background image

Technical Data

Effective:  May 1998

Page 

40

TD.44A.01.T.E

Cutler-Hammer

Magnum DS 
Metal-Enclosed 
Low-Voltage Switchgear

Typical Specification

General — Magnum DS indoor low-
voltage metal-enclosed switchgear 
shall consist of a stationary structure 
assembly and one or more removable 
Magnum DS power circuit breakers 
complete with disconnecting devices 
and other necessary accessories. The 
switchgear shall be suitable for 600 
volts maximum service and shall with-
stand a 2200 Vac dielectric test in 
accordance with ANSI standards. It 
shall be designed, manufactured and 
tested in accordance with the latest 
applicable standards of IEEE, NEMA, 
ANSI,  UL and CSA. Documentation 
of design testing shall be third-party 
certified.

Stationary Structure — Each steel unit 
forming part of the stationary assem-
bly shall be a self-contained housing 
having one or more individual breaker 
or instrument compartments, and a 
rear compartment for the buses and 
outgoing cable connections. 

Prying slots shall be provided on the 
base of the structures for ease of posi-
tioning in equipment rooms.

A rigid integral steel base shall be pro-
vided for each section, which will allow 
movement of shipping groups directly 
on rollers without the need for a sepa-
rate skid.

Each circuit breaker compartment shall 
be equipped with primary and second-
ary contacts, drawout extension rails, 
stationary levering mechanism parts, 
and required instrument current trans-
formers. A formed steel door, sup-
ported on concealed hinges with 
removable pins, shall be provided for 
each circuit breaker compartment. 
Access to the integral circuit breaker 
control panel, including the trip unit, 
shall be provided without the need to 
open the breaker compartment door. 
Closed-door spring charging and lever-
ing operations shall also be accom-
plished without the need to open the 
breaker compartment door.

The top of the unit shall be enclosed 
with removable steel sheets, which 
include necessary hooded ventilation 
openings. A separate removable 
access panel shall be provided for drill-
ing of control conduit hubs. A metal 
wireway with removable covers shall 
be provided for shipping-split wiring. 
Pull-apart type terminal blocks shall 
also be provided for rapid, error-free, 
shipping split assembly. A metal-
enclosed vertical wireway shall be 
provided for routing of field installed 
control wiring.

The structure shall be so designed that 
future additions may readily be made 
at any time. The steel structure shall be 
thoroughly cleaned and phosphatized 
prior to the application of the ANSI No. 
61 finish.

A white, laminated, plastic engraved 
circuit designation nameplate shall be 
provided on each circuit breaker door.

Buses and Connections — Each 
breaker circuit shall include the neces-
sary three-phase copper bus and con-
nections between the source bus and 
one set of circuit breaker studs. NEMA 
2-hole cable lugs, attached to silver-
plated copper extensions for the out-
going cables, shall be provided on the 
other set of circuit breaker studs. The 
buses and connections shall consist of 
high-conductivity (silver-plated) (tin-
plated) copper bar mounted on heavy-
duty supports, and having bolted 
joints. All bolted bus joints shall utilize 
Belleville type spring washers to main-
tain maximum joint integrity through 
continuous thermal cycling. The bus 
system shall be suitable for applica-
tions on power systems requiring a 
(100) (150) (200) kA short circuit with-
stand rating without upstream current 
limiting fuses.

Terminal blocks with integral-type 
barriers shall be provided for circuit 
breaker secondary circuits. The termi-
nal blocks shall be front accessible 
through a hinged access panel above 
each circuit breaker.

All control wiring shall be securely fas-
tened to the switchgear assembly with-
out the use of adhesive wire anchors. 
A dedicated wiring path shall be pro-
vided for purchaser’s installed control 
wiring. Non-adhesive anchors shall 
also be provided for anchoring of pur-
chaser’s installed wiring.

Disconnecting Devices — The station-
ary part of the primary disconnecting 
devices for each circuit breaker shall 
consist of a set of contacts extending 
through a glass polyester insulating 
base. Buses and outgoing cable termi-
nals shall be directly connected to 
them. The corresponding moving con-
tacts shall consist of a set of contact 
fingers suitably spaced on the circuit 
breaker studs. For ease of inspection 
and maintenance, contact fingers shall 
not be a permanent part of the station-
ary structure. In the “connected” posi-
tion, these contacts shall form a 
current-carrying bridge. The assembly 
shall provide a multitude of silver-to-

silver high-pressure point contacts. 
High uniform pressure on each finger 
shall be maintained by springs. The 
entire assembly shall be full floating 
and shall provide ample flexibility 
between the stationary and moving 
elements. Contact engagement shall 
be maintained only in the “connected” 
position.

The secondary disconnecting devices 
shall consist of floating fingers 
mounted on the stationary unit and 
automatically engages contacts 
located at the front of the compart-
ment. The secondary disconnecting 
contacts shall be silver-plated to insure 
permanence of contact. Contact 
engagement shall be maintained in the 
“connected” and “test” positions.

Removable Element — The removable 
element shall consist of a Magnum DS 
power circuit breaker equipped with 
the necessary disconnecting contacts 
and interlocks for drawout application. 
The removable element shall have 
four-position features and shall permit 
closing the compartment door with the 
breaker in the “connected,” “test,” and 
“disconnected” positions.

Power Circuit Breakers — The circuit 
breaker shall be Magnum DS, operat-
ing on the De-ion arc interruption prin-
ciple. These breakers shall incorporate 
specially designed circuit-interrupting 
devices that provide high interrupting 
efficiency and minimize the formation 
of arc flame and gases.

The primary contacts shall have an 
easily accessible wear indicator to indi-
cate main contact erosion. The breaker 
closing time shall be no more than 
three cycles. Each breaker shall have 
three windows in the front cover to 
offer clear indication of trip and close 
electrical accessories mounted in the 
breaker. The breaker shall be equipped 
with “De-ion” arc chutes which effec-
tively enclose the arcing contacts and 
confine the arc to reduce the distur-
bance caused by short-circuit interrup-
tion. Each breaker shall be equipped 
with a position indicator, mechanically 
connected to the circuit breaker mech-
anism.

www 

. ElectricalPartManuals 

. com 

Summary of Contents for Magnum DS

Page 1: ...nical Data Effective May 1998 Page 1 TD 44A 01 T E Cutler Hammer Magnum DS Metal Enclosed Low Voltage Switchgear New Information Mailed to E C 32 000B w w w E l e c t r i c a l P a r t M a n u a l s c...

Page 2: ...and 200 kA short circuit bus bracing without preced ing current limiting fuses Optional metal barriers isolates the cable compartment from the bus compartment Many other features for coordinated safe...

Page 3: ...as been tested for short circuit values of 85 000 amperes for a full 60 cycles Table R3 Standards Magnum DS switchgear conforms to the following standards NEMA SG3 and SG5 CSA ANSI C37 20 1 C37 51 and...

Page 4: ...otection In addition short delay protection may be set to the maximum instantaneous level effectively disabling short delay pro tection if instantaneous protection is turned off Under no condition is...

Page 5: ...400 400 1 25 1 50 1 75 2 00 2 50 3 00 3 75 5 00 600 600 1 25 1 50 1 75 2 00 2 50 3 00 3 75 5 00 800 800 1 25 1 50 1 75 2 00 2 50 3 00 3 75 5 00 1000 1000 1 25 1 50 1 75 2 00 2 50 3 00 3 75 5 00 1200...

Page 6: ...int indicated by rapid flashing of unit status LED on the product nominal occurs at 110 of the lr current with a 5 tolerance The short delay settings have conventional 100 5 as the pickup points 5 Wit...

Page 7: ...ing Plug ln 5 The instantaneous settings have conventional 100 10 as the pickup points 6 For additional curve tolerances contact Cutler Hammer 7 Total clearing times shown include the response times o...

Page 8: ...he rating plug is for 50 Hz and 60 Hz applications 8 Curves apply from 20 C to 50 C ambient temperatures above 95 C cause automatic trip 9 With zone interlocking on ground fault utilized and no restra...

Page 9: ...3 0 3 0 3 0 3 0 3 0 3 0 3 0 3 0 3 0 3 0 3 0 6 0 3 0 3 0 3 0 3 0 3 0 3 0 3 0 6 0 6 0 3 0 3 0 3 0 3 0 3 0 3 1 2 0 6 0 6 0 3 0 3 0 3 0 3 0 3 4000 4000 5 4000 1 0 3 0 3 0 3 0 3 0 3 5000 5000 5 5000 1 Refe...

Page 10: ...a clean dry room with filtered and or pressurized clean air This method permits the use of standard indoor switchgear and avoids the derating effect of non ventilated enclosures 3 Salt spray excessiv...

Page 11: ...mmable types of transformers eliminates necessity of vaults Efficient space utilization Advantages of Magnum DS Unit Substations Complete coordination both mechanical and electrical Extreme flexibilit...

Page 12: ...ar to those on radial unit substations If required and equipped with the appropriate relaying either trans former can be removed from service and isolated with no interruption of service on either bus...

Page 13: ...ith down stream devices Maximum capabilities of transformers of various types in terms of kVA and secondary current are given in Tables A1 through A4 It will be noted that the maximum ratings will oft...

Page 14: ...otors Contactors are recom mended for this application when there are a number of daily operations involved When system short circuits are less than 40 times the motor full load current the motor brea...

Page 15: ...ounded but in some very rare cases it is grounded at one corner of the delta or at some other point When the source is wye connected it can be grounded or ungrounded and when grounded the grounding is...

Page 16: ...solid state trip unit is in addition to the usual phase protection The ground element has adjustable pickup with calibrated marks as shown in Tables R8 and R9 and adjustable time delay The input curr...

Page 17: ...r equipment main tenance and hence reduce the occur rence of unplanned shutdowns Indication and Alarm Circuits When a fault is detected an adjustable time delay is provided to override tran sients Whe...

Page 18: ...hite pulse light off System control switch in normal position Reset control switch in either auto or manual Test Turn and hold the system control switch in the test position Phase B will be grounded v...

Page 19: ...formers HV 600 Max Delta To Distribution Equipment C B A 3 2 1 AM 51N Pulser Resistor Grounding Resistor G High Resistance Grounding Assembly Test Resistor Control Circuit CLF CLF CLF G R W Artificial...

Page 20: ...nded 20 20 Standard resid ual ground pro tection for single source systems and source ground per SK 5 for multiple ground sources Mini mum pickup 0 50 sec time delay Ground 3 wire or 4 wire as require...

Page 21: ...type of application Cutler Ham mer should be consulted for the actual bill of materials to be used The appli cation becomes rather complex if sin gle phase to neutral loads are being served X X N1 C B...

Page 22: ...Trip Unit GF Trip Unit GF Trip Unit 0 22 Sec 0 22 Sec 0 50 Sec 0 35 Sec GF Trip Unit TIE 52 1 52 T Bus 1 52 2 Bus 2 Bus 2 Neutral Connection Bus 1 Neutral Connection 52 T 33T 52 T Typical Feeder Thes...

Page 23: ...DS 608 MDS 408 MDS 408 MDS 408 MDS 408 MDS 408 MDS 408 1000 5 75 2778 50000 100000 150000 250000 500000 Unlimited 35900 41200 43300 45200 46700 48300 5600 41500 46800 48900 50800 52300 53900 MDS 632 M...

Page 24: ...DS 408 MDS 408 MDS 408 MDS 408 MDS 408 MDS 408 MDS 408 MDS 408 MDS 408 MDS 408 1500 5 75 1804 50000 100000 150000 250000 500000 Unlimited 20600 24900 26700 28400 29800 31400 7200 27800 32100 33900 356...

Page 25: ...08 MDS 408 MDS 408 MDS 408 MDS 408 MDS 408 MDS 408 MDS 408 MDS 408 MDS 408 1500 5 75 1443 50000 100000 150000 250000 500000 Unlimited 16500 20000 21400 22700 23900 25100 5800 22300 25800 27200 28500 2...

Page 26: ...eder 800 1600 2000 3200 Main 4000 5000 Main 4000 5000 Feeder 800 1600 2000 3200 Feeder 800 1600 2000 3200 Blank or Instrument 44 1118 Fig 6 44 1118 Fig 7 Maximum indoor shipping section width is 5 ver...

Page 27: ...Feeder 4000 5000 44 1118 Fig 11 44 1118 Fig 12 Maximum indoor shipping section width is 5 vertical sections or 120 inches 3048 mm whichever is smaller Maximum outdoor shipping width is 96 inches 2438...

Page 28: ...5000 Tie 4000 5000 Tie 4000 5000 Main 4000 5000 Feeder 800 1600 2000 3200 Feeder 800 1600 2000 3200 Blank or Instrument 44 1118 Fig 18 44 1118 Fig 19 Maximum indoor shipping section width is 5 vertic...

Page 29: ...ansformer connections etc All vertical sections are 92 inches 2339 mm high plus 4 inches 102 mm for ventilators and non removable lifting angle When a top of gear breaker lifter is used height is 99 i...

Page 30: ...izontal Cross Bus Area Vertical Bus Riser Area Lifting Plate Metal Enclosed Shipping Split Terminal Blocks Optional top of gear Breaker Lifter Magnum DS Metal Enclosed Low Voltage Switchgear Applicati...

Page 31: ...eft to right center of lineup From the front 26 inches 660 mm FC is the recommended front clearance for breaker removal with top of switchgear mounted breaker lifter If a portable breaker lifter is to...

Page 32: ...in 1829 mm 78 in 1981 mm 84 in 2134 mm 90 in 2286 mm 950 432 1000 455 1050 477 1100 500 1150 523 1200 545 11 in 279 mm Transition 60 in 1524 mm 66 in 1676 mm 72 in 1829 mm 78 in 1981 mm 84 in 2134 mm...

Page 33: ...ce interlocks are supplied on breakers and in compartments where the compartments are of the same physical size to assure an incorrect breaker cannot be inserted Key Interlock Switchgear Mounted Break...

Page 34: ...00 of main bus rating as standard Half 50 neu trals and neutral ratings up to a maxi mum of 6000 amperes are available as an option Ground A ground bus is furnished the full length of the switchgear a...

Page 35: ...cuit breaker The termi nal blocks are rated 30 amperes and will accept bare wire ring or spade ter minals for wire size ranges of 22 to 10 Extruded loops are punched in side sheets of the vertical wir...

Page 36: ...ndary Terminal Compartment Door Devices such as control push buttons breaker control switches indi cating lights and test switches can be mounted on these panels within space limitations The ammeters...

Page 37: ...he breaker closing springs are charged either through the manual charging handle or by the optional charging motor The breaker is mechanically interlocked to prevent closing of the breaker until the c...

Page 38: ...n the breaker Optional Breaker Attachments and Accessories a Shunt trip on manually operated breakers for any standard control voltage b Auxiliary contacts on manually or electrically operated breaker...

Page 39: ...CNC C5 CNO C11 CNO B30 B29 M M C7 C8 C10 C9 CNC CNO CNC B15 B14 C1 C2 C4 C3 C12 CNO C6 Breaker Auxiliary Contacts Shown with Breaker in Open Position Breaker Auxiliary Contacts Shown with Breaker in...

Page 40: ...tilize Belleville type spring washers to main tain maximum joint integrity through continuous thermal cycling The bus system shall be suitable for applica tions on power systems requiring a 100 150 20...

Page 41: ...y means of a portable plug in test device Both electrically operated and manu ally operated breakers shall have stored energy operating mechanisms The device to close the breaker shall be by means of...

Page 42: ...Technical Data Effective May 1998 Page 42 TD 44A 01 T E Cutler Hammer w w w E l e c t r i c a l P a r t M a n u a l s c o m...

Page 43: ...Technical Data Effective May 1998 Page 43 TD 44A 01 T E Cutler Hammer w w w E l e c t r i c a l P a r t M a n u a l s c o m...

Page 44: ...echnical Data Effective May 1998 Page 44 TD 44A 01 T E Printed in U S A Cutler Hammer Cutler Hammer Magnum DS Metal Enclosed Low Voltage Switchgear w w w E l e c t r i c a l P a r t M a n u a l s c o...

Reviews: