Detectors/Devices Menu
Page 43
Normal Alarm - NA (03)
When triggered, a zone of type Normal Alarm will start an alarm provided the system
is set.
When the control unit first learns a radio detector, the zone type defaults to Normal
Alarm.
24 Hour Alarm - 24 (04)
Activating this zone while the system (or partition) is unset causes an internal alarm
(internal sounders and speakers only). Activating this zone while the system (or
partition) is set causes an alarm from internal and external sounders.
Final Exit
– FE (05)
Zones of this type must be the last detector to be activated on exit, or the first to be
activated on entry. You can use zones of this type to complete the setting of the
system or partition, or to start the entry procedure. See page 72 to set the exit mode
type.
Note:
If you give a Final Exit zone any of the Part Set attributes, you can program
that zone to behave like a Normal Alarm zone if the user part sets the system. See
page 78.
Entry Route
– ER (06)
Use this zone type for detectors sited between the Final Exit door/detector and the
keypad. If the entry/exit timer is running when an Entry Route zone is triggered, no
alarm occurs until the entry/exit timer expires.
Note:
If you give an Entry Route zone one of the Part Set attributes, you can
program that zone to behave like a Final Exit zone if the user part sets the system.
See page 78.
Technical Alarm
–TA (07)
Use this zone type when you want to monitor equipment, for example a freezer,
without raising a full alarm. If a Technical Alarm zone is activated, the control unit
logs the event, generates a fault condition, and (if the control unit is correctly
programmed, see page 102) starts communication.
If the technical alarm occurs while the system is set, the system makes no audible
alarm. When a user unsets the system, the keypad shows an alert.
If a Technical Alarm zone is activated while the system is unset, the system starts an
alert immediately and gives a brief tone from the keypad every few seconds. When a
user enters a valid access code, the keypad stops the tone and displays the zone
causing the alarm.
When the user acknowledges the alert by pressing
, the control unit resets the
technical alarm ready for the next event.
Note that a tamper on a Technical Alarm zone when the system is unset will cause
an internal alarm.
Key Switch Moment.
– KSM (08)
Use this zone type to connect a momentary keyswitch to a single zone.
In a part-setting system, the keyswitch can full set or unset.
In a partitioned system, you can allocate the keyswitch to one or more partitions.
Each time a user operates the keyswitch, the control unit changes the current set
state.
Key Switch Latched
– KSL (09)
Use this zone type to connect a fixed position keyswitch to a single zone.