4 Short-circuit / motor protection
4.2 Motor protection
36
EMS2…-SWD Electronic motor starter
10/19 MN120008EN
www.eaton.com
4.2.4 Setting of the motor protection
Proceed as follows in order to configure the motor protection:
▶
1. Create a SWD configuration in offline mode.
▶
2. Select the EMS2-…-SWD module.
▶
3. Set the motor protection in the “Device parame-
ters” tab.
▶
4. Select a communications display.
▶
5. Select an interface of the PC for the communi-
cation.
▶
6. Select the key panel “online”.
▶
7. Download the configuration by pressing the
“PC => device” button.
→
The
PWR
LED on the EMS2-…-SWD motor
starter flashes.
The LEDs below this indicate the sent value for
the motor protection (see table 11 below).
▶
8. Press the RESET button on the front of the
motor starter for at least one second.
→
This makes the device adopt the sent value
(only for motor protection 1) and the
PWR
LED
now lights up permanently again.