4 Short-circuit / motor protection
4.2 Motor protection
EMS2…-SWD Electronic motor starter
10/19 MN120008EN
www.eaton.com
37
4.2.5 Checking the set value
▶
Press the set button for longer than 2 seconds.
→
The LED
PWR
flashes:
At 20 % on and 80 % off, the setting of motor protection 1 is displayed;
with 50 % on and 50 % off, the setting of motor protection 2 is dis-
played.
→
The four remaining LEDs (
SWD
,
ERR
,
L
,
R/ON
) indicate the set value
(for coding, see table 11 below. 0 = off, 1 = on).
▶
Release the set button.
→
The LED
PWR
lights up permanently again:
Table 11: Settings of the motor protection
Code
Setting I
n
PWR
ERR
L
R
I
e
= 3 A
(EMS2-…-3-SWD)
I
e
= 9 A
(EMS2-…-9-SWD)
PWR
ERR
–
ON
A
A
0
0
0
0
0.18
1.5
0
0
0
1
0.3
2.0
0
0
1
0
0.44
2.5
0
0
1
1
0.6
3.0
0
1
0
0
0.68
3.5
0
1
0
1
0.88
4.0
0
1
1
0
1.0
4.5
0
1
1
1
1.1
5.0
1
0
0
0
1.2
5.5
1
0
0
1
1.5
6.0
1
0
1
0
1.6
6.5
1
0
1
1
1.9
7.0
1
1
0
0
2.1
7.5
1
1
0
1
2.4
8.0
1
1
1
0
2.7
8.5
1
1
1
1
3.0
9.0