3 Communication via SmartWire-DT (SWD)
3.4 Input and output data
24
EMS2…-SWD Electronic motor starter
10/19 MN120008EN
www.eaton.com
Byte 2: Motor current [%]
Byte 3: Thermal load [%]
Bit
7
6
5
4
3
2
1
0
Configura-
tion
I-REL
(MSB)
I-REL
I-REL
I-REL
I-REL
I-REL
I-REL
I-REL
(LSB)
Bit
Designation
Meaning
0, 1, ... ,7
I-REL
Motor current in percent (highest value of the three phase currents)
Value range: 0 - 255 % I
e
(100 %
≙
3 A or 9 A, depending on type)
Bit
7
6
5
4
3
2
1
0
Configura-
tion
TH
(MSB)
TH
TH
TH
TH
TH
TH
TH
(LSB)
Bit
Designation
Meaning
0, 1, ... ,7
TH
Current calculated thermal load of the motor
Value range: 0 - 255 % of the current that has been set with the motor
protection function I
n