3 Communication via SmartWire-DT (SWD)
3.4 Input and output data
EMS2…-SWD Electronic motor starter
10/19 MN120008EN
www.eaton.com
25
Byte 4: Device type, status information 2
Byte 5, 6: Motor current [A] (16-bit data word)
Bit
7
6
5
4
3
2
1
0
Configura-
tion
OL-WARN MAINS
FAILURE
–
OK
TYPE
(MSB)
TYPE
TYPE
TYPE
(LSB)
Bit
Designation
Meaning
0, 1, 2, 3
TYPE
Type of motor starter EMS2-…-SWD
4
OK
1: The device is activated and current is flowing.
5
–
Not used
6
MAINS FAILURE
1: The device is activated; but there is no current.
7
OL-WARN
Current calculated thermal load of the motor
0: Load < 105 % of the set current I
n
1: Load > 105 % of the set current I
n
Byte 5 / Bit 7
6
5
4
3
2
1
0
Configura-
tion
I-ABS
I-ABS
I-ABS
I-ABS
I-ABS
I-ABS
I-ABS
I-ABS
(LSB)
Byte 6 / Bit 7
6
5
4
3
2
1
0
Configura-
tion
I-ABS
(MSB)
I-ABS
I-ABS
I-ABS
I-ABS
I-ABS
I-ABS
I-ABS
(LSB)
Bit
Designation
Meaning
0, 1, ... ,15
I-ABS
Motor current in amps (highest value of the three phase currents)
Resolution: 10 mA
Example: 357
≙
3.57 A
Bit 3
Bit 2
Bit 1
Bit 0 Type
0
0
0
0
not used
0
0
0
1
not used
0
0
1
0
not used
0
0
1
1
not used
0
1
0
0
EMS2-DO-T-3-SWD
0
1
0
1
EMS2-RO-T-3-SWD
0
1
1
0
EMS2-DOS-T-3-SWD
0
1
1
1
EMS2-ROS-T-3-SWD
1
0
0
0
EMS2-DO-T-9-SWD
1
0
0
1
EMS2-RO-T-9-SWD
1
0
1
0
EMS2-DOS-T-9-SWD
1
0
1
1
EMS2-ROS-T-9-SWD
1
1
0
0
not used
1
1
0
1
not used
1
1
1
0
not used
1
1
1
1
not used