7 Technical data
EMS2…-SWD Electronic motor starter
10/19 MN120008EN
www.eaton.com
51
7 Technical data
Size/feature
EMS2-…-3-SWD
EMS2-…-9-SWD
Standards
For EMS2-D(R)O-…-SWD devices
without safety function:
IEC/EN 60947-1
IEC/EN 60947-4-2
For EMS2-D(R)OS-…-SWD devices
with safety function:
IEC/EN 60947-1
IEC/EN 60947-4-2
IEC 61508
ISO 13849
For EMS2-D(R)O-…-SWD devices
without safety function:
IEC/EN 60947-1
IEC/EN 60947-4-2
For EMS2-D(R)OS-…-SWD devices
with safety function:
IEC/EN 60947-1
IEC/EN 60947-4-2
IEC 61508
ISO 13849
Ambient conditions and mounting
Ambient temperature during operation
-5 °C - +55 °C
Condensation not permissible – prevent with
suitable measures! Observe derating!
-5 °C - +55 °C
Condensation not permissible – prevent with
suitable measures! Observe derating!
Storage temperature, permissible
-40 °C - + 80 °C
-40 °C - + 80 °C
Degree of protection
IP20
IP20
Degree of pollution
2
2
Dimensions
section 8, “Dimensions”, page 55
section 8, “Dimensions”, page 55
Mounting
on 35-mm top-hat rail according to
IEC/EN 60715
on 35-mm top-hat rail according to
IEC/EN 60715
Mounting position
Vertical, motor feeder on bottom
Vertical, motor feeder on bottom
EMC
Emitted interference is cable related:
EN 55011, class A
Emitted interference is radiated:
EN 61000-6-3, class A
This is a product for environment A.
In a domestic environment, this device may
cause radio interference, in which case the user
may be required to take adequate measures.
Emitted interference is cable related:
EN 55011, class A
Emitted interference is radiated:
EN 61000-6-3, class A
This is a product for environment A.
In a domestic environment, this device may
cause radio interference, in which case the user
may be required to take adequate measures.
Connections
Cross-section - control cables
0.2 mm² - 2.5 mm²
AWG 24 - 14
0.2 mm² - 2.5 mm²
AWG 24 - 14
Cross-section - power cables
0.2 mm² - 2.5 mm²
AWG 24 - 14
0.2 mm² - 2.5 mm²
AWG 24 - 14
Stripping length
10 mm
10 mm
Supply of the device / the control inputs
Overvoltage category
III
III
Rated control voltage U
AUX
(from SWD)
24 V DC
24 V DC
Range of the control supply voltage
19.2 V DC - 30 V DC
19.2 V DC - 30 V DC
Rated control current I
S
60 mA
60 mA
Rated actuating voltage U
C
(EN+/EN-)
24 V DC
24 V DC
Rated actuating current I
C
7 mA
7 mA
Switching threshold
LOW < 9.6 V DC
HIGH > 19.2 V DC
LOW < 9.6 V DC