6 Status messages
6.1 LEDs on the front of the device
46
EMS2…-SWD Electronic motor starter
10/19 MN120008EN
www.eaton.com
The status LEDs in combination provide information about the device status.
Table 12: Status messages – as a combination of the five LEDs
LED does not light up
LED lights up
LED flashing
X
Any status
LED
Status
Description
Reset
See also
“Resetting after an error
message”, page 48
PWR
SWD
ERR
L
(–)
R
(ON)
Off
No supply voltage
available
–
/
X
X
X
No SWD
Device not integrated into SWD
–
/
Data traffic
Device integrated into SWD.
Cyclical or acyclical communica-
tion is taking place.
–
Drive switched on
Counterclockwise operation (L)
–
Drive switched on
Clockwise operation (R or ON)
–
Internal error
Device needs to be replaced
Not possible
X
Motor protection tripped
during counterclockwise oper-
ation
Motor protection in cooling-
down phase,
Reset not possible.
Manually after a cooling-
down time of approx. 2 min;
automatically after approx.
20 min