6. Just as with any parameter change, the final step is to transfer the modifcations to
the protection device (keys »F7« or »Ctrl«+»F7«, or menu items [Device → Transfer
ALL Parameters into the Device], [Device → Transfer only modified Parameters into
the Device].
Ctrl . Single Line
BusbarFeeder
Module . Name
Value
Device Planning
Single-line Diagram
Single-line Name:
Single-line Error Messages:
Apply
Cancel
Help
Single-line Diagram...
BusbarFeeder
QA1
Controlled Make Break SG
Name
Type
SG #
SG 1
Switchgear Properties:
IA
IB
0 A
(local_remote)
IC
QA1
0 A
0 A
!
E_FB
G
1
2
3
After having transferred the
*.ErPage
file to the EMR-3MP0, the Measurement Page
becomes part of the device settings. This means that if PowerPort-E saves the settings
onto the PC as an
*.ErPara
file (see
╚═▷ “1.3 Types of Settings, Signals and Values”
), the
Measurement Page is also saved. Therefore you do not need the
*.ErPage
file again
when you configure the next EMR-3MP0, it is sufficient to open the
*.ErPara
file in
PowerPort-E and transfer it to the EMR-3MP0.
55
www.eaton.com
EMR-3MP0
1 EMR‑3MP0 Motor Protection Relay
1.6 Measuring Values