![background image](http://html1.mh-extra.com/html/eaton/cutler-hammer-iq-300-series/cutler-hammer-iq-300-series_instructions-for-installation-operation-and-maintenance_3796396074.webp)
IL17574C
Page 5-8
Effective Date: 2/04
IQ 300
Page 5-8
Effective Date: 2/04
For more information visit:
www.cutler-hammer.eaton.com
Table 5.6 Slave Action Definitions
Byte2
Byte1 Byte0
Definition
0
0
4
Reset Peak Demand Watts
0
0
8
Reset Energy (kWh) and input counters
0
0 40h
Reset (synchronize) Demand Watts Window
0
0
80h
Snapshot Energy
0
1
1
Reset Peak Demand Currents
0
1
4
Reset all Min/Max values
0
1
6
Reset input counters
0
1
13
Reset Min/Max Currents
0 1
14
Reset Min/Max L-L Voltages
0
1
15
Reset Min/Max L-N Voltages
0
1
16
Reset Min/Max Power Factor-Apparent
0 1
17
Reset Min/Max Power Factor-Displacement
0
1
18
Reset Min/Max Power
3
0
2
Reset INCOM Slave Interface Statistics
3
0
3
Reset product specific statistics
3
0
6
Acknowledge energy reset
4
1
X
Activate Relay Output #X
(X = relay output number: 1 or 2)
4
2
X
De-activate Relay Output #X
(X = relay output number 1 or 2)
6
6
0
Acknowledge Digital Input Reset