5.3
FUNCTION CODES
The IQ 300 responds to a limited number of MODBUS function codes. These are
function codes 04 and 10 hex.
5.4
BLOCK OF REGISTERS
Using the 04 MODBUS command you can read any block from table 5.1. The
beginning address and the size of the block are the elements of the 04 command.
Below is an example of message for retrieval of data.
Table 5.1 IQ 300 Objects Cont.
Objects - (complete list)
Units
Modbus
Address (hex)
INCOM Products -
(partial list)
Name
Numeric
Fixed point
(FP)
(hex)
FP
scale
factor
IQ-
300
power
A ph
W
183A
1
x
B
ph
W
183C
1
x
C
ph
W
183E
1
x
reactive A ph
VAR
1840
1
x
reactive B ph
VAR
1842
1
x
reactive C ph
VAR
1844
1
x
apparent A ph
VA
1846
1
x
apparent B ph
VA
1848
1
x
apparent C ph
VA
184A
1
x
power factor
displacement A ph
pf
184C
100
x
displacement B ph
pf
184E
100
x
displacement C ph
pf
1850
100
x
apparent A ph
pf
1852
100
x
apparent B ph
pf
1854
100
x
apparent C ph
pf
1856
100
x
power peak
demand
W 1858
1 x
source 1
V
AB
V 185A 10
V
BC
V 185C 10
V
CA
V 185E 10
freq
Hz
1860
10
source 2
V
AB
V 1862 10
V
BC
V 1864 10
V
CA
V 1866 10
freq
Hz
1868
10
power
power (real 3 ph)
W
186A
1
x
power factor
pf (*)
pf
186C
100
x
prod ID
prod ID
186E x
frequency freq Hz
1870
100
x
energy forward
kWh
1872 1
x
reverse
kWh
1874
1
x
net
kWh
1876
1
x
reactive
energy lead kVARh
1878 1 x
lag
kVARh
187A
1
x
net
kVARh
187C
1
x
energy (4 reg)
apparent
kVAh
187E
1
x