4.10.1 Password Setup
Scroll up and down the Edit Menu options, when you reach Password press enter.
The screen changes to show the digits of the current password blinking. To change
any digit of the password, first select it by pressing Enter to move the blinking to the
desired digit. Then use the Scroll up arrow to increase the digit or the Scroll down
arrow to decrease the digit. When the desired choice is displayed, press Enter to
lock in the selection.
This screen also allows the user to specify if a password is required to change the
IQ 300 set points or system parameters and shows the user what the password is or
would be if it were in use.
The screen initializes when Password Y is selected. To specify if a password is
required, press either of the Scroll arrows to toggle between Y and N. When the
desired choice is displayed, press Enter to lock in the selection.
If the procedure completes successfully, Download OK
appears briefly. The display
then returns to the previous screen.
If an error occurs in the New Password selection process, an error message
displays. Press Enter to return to the previous screen, and repeat the steps above.
4.10.2 INCOM™ Setup (IQ 320 and IQ 330 Base Modules only)
Note:
A display is required to configure the INCOM™ address.
To set these values on IQ 320 and IQ 330 Base modules installed without a
permanently connected IQ 300 display module, temporarily connect an IQ 300
display module and follow the procedure below.
Scroll up or down the Edit Menu options, when you reach the INCOM RATE option
or the INCOM ADDR option, press the enter button.
The INCOM RATE screen, shown in figure 4.27, displays the baud rate at which the
IQ 320 and IQ 330 will communicate over the PowerNet network. The INCOM
ADDR screen, shown in figure 4.28, indicates the network address (in hexadecimal)
currently assigned to the IQ 320 or IQ 330.
The screen initializes with Baud Rate
selected and the current value displayed. To
select a baud rate at which the IQ 320 or IQ 330 will communicate over the
PowerNet network, press either of the
Scroll
arrows to step through the choices
9600 or 1200 baud
.
When the desired choice is displayed, press
Enter
to lock in the
selection.
XXXX
INCOM RATE
Figure 4.27 Incom
Rate Display
XXX
INCOM ADDR
Figure 4.28 Incom
Address Display