For more information visit: www.eaton.com
IB ATS-1005
Instructional Booklet
Page
10
Effective: March 2010
Instructions for Installation, Operation and Maintenance of the
Eaton ATC-600 Automatic Transfer Switch Controller
2.5 Specification Summary
Refer to Table
1
.
Table 1. ATC-600 Specifications
PARAMETER
SPECIFICATION
Control Power:
• 120Vac (50/60 Hz) (operating range 65 to 160 Vac)
Power Consumption:
• 18VA
Environmental Conditions:
Operating Temperature
• -20° to 70°C
Operating Humidity
• up to 90% Relative Humidity (non-condensing)
Enclosure Compatibility:
• NEMA 12 (standard mounting)
• NEMA 4/4X (mounted with gasket between panel and device faceplate)
• NEMA 3R (outdoor)
• UV Resistant ATC-600 Faceplate
System Voltage Application:
• 120 to 600 Vac (50/60 Hz) (single or three phase)
Voltage Measurements:
• Source 1, Source 2 and Load (VAB, VBC, VCA for Three Phase System)
Voltage Measurement Range:
• 0 to 700 Vac
Voltage Measurement Accuracy:
• ±1% of Full Scale
Frequency Measurements:
• Source 1 and Source 2
Frequency Measurement Range:
• 40 to 80 Hz
Frequency Measurement Accuracy:
• ±0.1 Hz
Undervoltage Dropout Range (Volts)
Breaker Switch Style ATS
50 to 97% of Nominal System Voltage
Undervoltage Pickup Range (Volts)
Breaker Switch Style ATS
(D2%) to 99% of Nominal System Voltage
Overvoltage Dropout Range (Volts)
Breaker Switch Style ATS
105 to 120% Nominal System Voltage
Overvoltage Pickup (Volts)
Breaker Switch Style ATS
103% to (Dropout-2%) of Nominal System Voltage
Underfrequency Dropout (Hertz)
Breaker Switch Style ATS
90 to 97% of Nominal System Frequency
Underfrequency Pickup (Hertz)
Breaker Switch Style ATS
(D1 Hz) to 99% of Nominal System Frequency
Overfrequency Dropout (Hertz)
Breaker Switch Style ATS
103 to 110% of Nominal System Frequency
Overfrequency Pickup (Hertz)
Breaker Switch Style ATS
101% to (Dropout -1 Hz) of Nominal System Frequency
Applicable Testing:
• UL Recognized Component
• Meets Seismic Requirements of Uniform and California Building Codes
(exceeding requirements of worst case Zone 4 levels)
• Complies with UL 991 environmental tests
• Complies with IEC 61000-4-2, 61000-4-3, 61000-4-4, and 61000-4-5
• Complies with CISPR 11, Class A
• Complies with FCC Part 15, Subpart B, Class A