4–20kVA Users Guide P-164000669 4–20kVA Users Guide P-164000669—Rev 09
83
In/Out Settings
The In/Out Settings menus allows control of input and output limits.
Figure 65. In/Out Settings Menu
Local Settings
In/Out settings
On/Off settings
Battery settings
Input signals
Comm settings
User password enable
User password settings
Settings
Output voltage
High Efficiency mode
Protected Bypass
Overload prealarm
Redundancy
Byp freq limit
Byp volt min limit
Byp volt max limit
In/out settings
Output voltage
110 V
√
120 V
127 V
High Efficiency mode
Disabled
√
Enabled
Protected Bypass
Enabled
√
Disabled
Overload prealarm
100
Byp freq limit
Byp volt min limit
Byp volt max limit
Redundancy
Level 0
Level 1
Level 2
%
Level 3
Level 4
4
Hz
12
%
12
%
[110V] [120V][127V]
Default:[120V][127V]
[Enabled] [Disabled]
Power the output from
Default: Disabled
[Enabled] [Disabled]
Default: Enabled
[10%] … [102%]
Load % when overload
alarm occurs
Default: 100%
Set redunancy level
Default: 0
Default disables
transfer to Bypass if the
measured bypass
frequency is below
the nominal 4%
Default disables
transfer to Bypass if the
measured bypass voltage
level is below the nominal
output voltage minus 12%
Default disables
transfer to Bypass if the
measured bypass voltage
level is above the nominal
output voltage plus 12%
Summary of Contents for 9PXM
Page 1: ...p n P 164000669 Revision 09 Eaton 9PXM UPS 4 20kVA Users Guide Eaton 9PXM UPS ...
Page 4: ......
Page 8: ...viii 4 20kVA Users Guide P 164000669 4 20kVA Users Guide P 164000669 Rev 09 Table of Contents ...
Page 12: ...xii 4 20kVA Users Guide P 164000669 4 20kVA Users Guide P 164000669 Rev 09 List of Figures ...
Page 14: ...xiv 4 20kVA Users Guide P 164000669 4 20kVA Users Guide P 164000669 Rev 09 List of Tables ...
Page 22: ...8 4 20kVA Users Guide P 164000669 4 20kVA Users Guide P 164000669 Rev 09 Physical Features ...
Page 110: ...96 4 20kVA Users Guide P 164000669 4 20kVA Users Guide P 164000669 Rev 09 Communication Slots ...
Page 130: ...P 16400066909 P 164000669 09 ...