32
4–20kVA Users Guide P-164000669 4–20kVA Users Guide P-164000669—Rev 09
Figure 27. Bypass From UPS to LINE
Depress and HOLD
red button
Rotate switch
to LINE position
LINE
MODE
UTILITY
LOAD
BPM
UPS
FROM
UPS
TO
UPS
INPUT
OUTPUT
INPUT
OUTPUT
2.
Turn the switch from LINE to SERVICE (see
). The critical load is fed directly from utility and the
UPS is now completely disconnected from AC power. Ensure that the UPS is off and the terminals are
completely de-energized before performing any maintenance on the UPS.
Figure 28. Bypass From LINE to SERVICE
Rotate switch
to SERVICE position
SERVICE
MODE
UTILITY
LOAD
BPM
UPS
FROM
UPS
TO
UPS
INPUT
OUTPUT
INPUT
OUTPUT
33..88
LLoocckk--oouutt//TTaagg--oouutt
The BPM comes with a Lock-out/Tag-out (LOTO) feature to keep the BPM bypass switch locked in SERVICE
mode while qualified service personnel works on the UPS. To use the LOTO feature:
1.
Press and hold the red bar (See
).
Summary of Contents for 9PXM
Page 1: ...p n P 164000669 Revision 09 Eaton 9PXM UPS 4 20kVA Users Guide Eaton 9PXM UPS ...
Page 4: ......
Page 8: ...viii 4 20kVA Users Guide P 164000669 4 20kVA Users Guide P 164000669 Rev 09 Table of Contents ...
Page 12: ...xii 4 20kVA Users Guide P 164000669 4 20kVA Users Guide P 164000669 Rev 09 List of Figures ...
Page 14: ...xiv 4 20kVA Users Guide P 164000669 4 20kVA Users Guide P 164000669 Rev 09 List of Tables ...
Page 22: ...8 4 20kVA Users Guide P 164000669 4 20kVA Users Guide P 164000669 Rev 09 Physical Features ...
Page 110: ...96 4 20kVA Users Guide P 164000669 4 20kVA Users Guide P 164000669 Rev 09 Communication Slots ...
Page 130: ...P 16400066909 P 164000669 09 ...