Chhaapptteerr 55 B
Baatttteerryy C
Caabbiinneett IInnssttaallllaattiioonn
55..11
S
Sttaannddaarrdd B
Baatttteerryy C
Caabbiinneett IInnssttaallllaattiioonn
WARNING
Only qualified service personnel (such as a licensed electrician) should perform the battery cabinet installation.
Risk of electrical shock.
CAUTION
•
Before connecting an external battery cabinet to the UPS cabinet or to another external battery cabinet,
verify that all AC input power is removed from the UPS. Open the input service circuit breaker or turn the
external bypass switch to the SERVICE position.
•
Remove all battery modules in the UPS cabinet and/or battery cabinet to ensure DC voltage is removed
from the internal DC buses.
•
In the UPS cabinet, the proper location of cabinet-to-cabinet DC wiring is on the lower left of the rear panel.
•
In the external battery cabinets P-103003632 , and P-103003727 this wiring installs into the rear panel
where the DC emergency disconnect switch is located on the lower left of the rear panel. See
.
•
All of the slots in the Standard 8 and 12 slot battery cabinets can be populated with batteries.
Figure 37. Standard EBM Front and Back
Battery
Modules
Battery
Modules
EBM Front View
(Covers removed)
UPS DC
Terminal
Covers
DC Emergency
Disconnect
Switch
EBM
EBM Front
EBM Back
Prepare the EBM Cabinet
Summary of Contents for 9PXM
Page 1: ...p n P 164000669 Revision 09 Eaton 9PXM UPS 4 20kVA Users Guide Eaton 9PXM UPS ...
Page 4: ......
Page 8: ...viii 4 20kVA Users Guide P 164000669 4 20kVA Users Guide P 164000669 Rev 09 Table of Contents ...
Page 12: ...xii 4 20kVA Users Guide P 164000669 4 20kVA Users Guide P 164000669 Rev 09 List of Figures ...
Page 14: ...xiv 4 20kVA Users Guide P 164000669 4 20kVA Users Guide P 164000669 Rev 09 List of Tables ...
Page 22: ...8 4 20kVA Users Guide P 164000669 4 20kVA Users Guide P 164000669 Rev 09 Physical Features ...
Page 110: ...96 4 20kVA Users Guide P 164000669 4 20kVA Users Guide P 164000669 Rev 09 Communication Slots ...
Page 130: ...P 16400066909 P 164000669 09 ...