70
Eaton 93PM UPS 480V Three-Wire – 100 kW Frame Installation and Operation Manual 164000227—Rev 07
Table 19. Normally-Closed REPO Connections and Wire Terminations
From REPO
Station
Switch
Contact Block
(Either Block)
UPS
REPO
Terminal
Name
Description
Recommended
Minimum
Wire Size
Size of
Wire
Termination
Tightening
Torque
3 NO
1
EPO_A_
B
Input: Normally-closed
dry contact used to
activate UPS EPO from
a remote switch.
Twisted Pair Wires
#18 AWG
#16-#30 AWG
2 lb in
(0.22-0.25 Nm)
4 NO
2
GND-ISO
Figure 37. Normally-Closed REPO Switch Wiring
3
1
2
4
1
2
REPO
Switch
(NC)
Twisted
Wires
REPO TB
44..1133
IInniittiiaall S
Sttaarrttuupp
Startup and operational checks for parallel systems or installations with accessory cabinets must be performed
by an authorized Eaton Customer Service Engineer, or the warranty terms specified on the product's resources
page become void. See
for details. This service is offered as part of the sales contract for
the UPS. Contact an Eaton service representative in advance (usually a two-week notice is required) to reserve
a preferred startup date.