Eaton 93PM UPS 480V Three-Wire – 100 kW Frame Installation and Operation Manual 164000227—Rev 07
55
Figure 26. Building Alarm Terminal Block Connector Assignments
UPS Building Alarms
1 2 3 4 5 6 7 8 9 10
Building Alarm 5
Building Alarm 5 Return
Building Alarm 4
Building Alarm 4 Return
Building Alarm 1 Return
Building Alarm 1
Building Alarm 2 Return
Building Alarm 2
Building Alarm 3 Return
Building Alarm 3
Table 14. Relay Contact Connections and Wire Terminations
Terminal
Name
Description
Recommended
Wire Size
Size of
Pressure
Termination
Tightening
Torque
1
Relay Contact NC
Output: General purpose
normally-closed (NC) relay
contact
Twisted
Pair Wires
#18 AWG
#14-#30 AWG
2 lb in
(0.22-0.25 Nm)
3
Relay Contact
Common
2
Relay Contact NO
Output: General purpose
normally-open (NO) relay
contact
3
Relay Contact
Common
Figure 27. Relay Contact Terminal Block Connector Assignments
UPS Relay Output
1 2 3
NO_Out
NC_Out
Com
44..1111..22 IInnssttaalllliinngg B
Baatttteerryy D
Deetteecctt IInntteerrffaaccee C
Coonnnneeccttiioonnss
NOTE 1
The UPS battery detect signal uses a UPS building alarm input to indicate an open
battery breaker.
NOTE 2
Any pair of unused building alarm terminals may be used for the battery detect
connections.
NOTE 3
Program the battery detect building alarm to read battery open and for normally open
contacts.
NOTE 4
If installing interface wiring connections between standalone cabinets, conduit must be
installed between cabinets.
NOTE 5
Disconnect terminal block plugs from terminal blocks to wire plugs.