Eaton 93PM UPS 480V Three-Wire – 100 kW Frame Installation and Operation Manual 164000227—Rev 07
31
Table 7. Power Cable Conduit Recommendations: Eaton 93PM-100-1 and Eaton 93PM-100-2 (N+1) (Continued)
UPS Model
UPS
Rating
Voltage
Terminal
Number
of Wires
in Conduit
Minimum
Conduit
Trade
Size
Number
of
Conduits
Eaton 93PM-100-1
Eaton 93PM-100-2
(N+1)
50 kW
480 Vac
AC Input to UPS
Rectifier and Bypass
(A, B, C, Ground)
4
1-1/4
1
AC Output (Three Wire)
(A, B, C, Ground)
4
1
1
DC
Battery
(Positive, Negative, Ground)
5
2-1/2
1
NOTE
Wires per conduit include ground wire.
Table 8. Power Cable Conduit Recommendations: Eaton 93PM-100-2 and Eaton 93PM-100-3 (N+1)
UPS Model
UPS
Rating
Voltage
Terminal
Number
of Wires
in Conduit
Minimum
Conduit Trade
Size
Number
of
Conduits
Eaton 93PM-100-2
Eaton 93PM-100-3
(N+1)
60 kW
480 Vac
AC Input to UPS
Rectifier and Bypass
(A, B, C, Ground)
4
1-1/2
1
AC Output (Three Wire)
(A, B, C, Ground)
4
1-1/4
1
DC
Battery
(Positive, Negative, Ground)
5
2-1/2
1
Eaton 93PM-100-2
Eaton 93PM-100-3
(N+1)
70 kW
480 Vac
AC Input to UPS
Rectifier and Bypass
(A, B, C, Ground)
4
1–1/2
1
AC Output (Three Wire)
(A, B, C, Ground)
4
1-1/4
1
DC
Battery
(Positive, Negative, Ground)
5
2-1/2
1
Eaton 93PM-100-2
Eaton 93PM-100-3
(N+1)
80 kW
480 Vac
AC Input to UPS
Rectifier and Bypass
(A, B, C, Ground)
4
2
1
AC Output (Three Wire)
(A, B, C, Ground)
4
1-1/2
1
DC
Battery
(Positive, Negative, Ground)
5
2-1/2
1
Summary of Contents for 93PM Series