Eaton 93PM UPS 480V Three-Wire – 100 kW Frame Installation and Operation Manual 164000227—Rev 07
29
Table 5. Input/Output Ratings and External Wiring Recommendations: Eaton 93PM-100-2 and 93PM-100-3 (N+1)
(Continued)
Minimum Conductor Size (Phase Pos. and Neg.)
Number per Pole
AWG or kcmil
(each)
3/0
(2)
3/0
(2)
3/0
(2)
3/0
(2)
3/0
(2)
Minimum Conductor Size (Ground)
Number
–
AWG or kcmil
(each)
4
(1)
4
(1)
4
(1)
4
(1)
4
(1)
AC Output to Critical Load (Three Wire)
Full Load Current
(3) Phases, (1) Ground
D
Amps
72
84
96
108
120
Minimum Conductor Size (Phase A, B, and C)
Number per Phase
AWG or kcmil
(each)
3
(1)
2
(1)
1
(1)
1/0
(1)
2/0
(1)
Minimum Conductor Size (Ground)
Number
–
AWG or kcmil
(each)
8
(1)
6
(1)
6
(1)
6
(1)
6
(1)
NOTE
Callout letters
A
,
B
,
C
and
D
map to
through
.
NOTE
Line-up-and-match battery wiring with a 105°C rating is factory supplied with the Eaton 93PM Integrated Battery Cabinet
(IBC).
The power wiring terminals are pressure terminations, UL and CSA rated. See
for external power cable
terminations.
and
show the location of the UPS power cable terminals.
Table 6. UPS External Power Cable Terminations
Terminal Function
Terminal
Function
Number and Size
of Pressure Termination
AWG or kcmil
Tightening
Torque
Nm (lb in)
Screw Size
and Type
AC Input to UPS Rectifier
E1
Phase A
2 - #6-250 kcmil
22.6 (200)
1/4" Hex
E2
Phase B
2 - #6-250 kcmil
22.6 (200)
1/4" Hex
E3
Phase C
2 - #6-250 kcmil
22.6 (200)
1/4" Hex
AC Input to Bypass
E6
Phase A
2 - #6-250 kcmil
22.6 (200)
1/4" Hex
E7
Phase B
2 - #6-250 kcmil
22.6 (200)
1/4" Hex
E8
Phase C
2 - #6-250 kcmil
22.6 (200)
1/4" Hex
AC Output to Critical Load
E9
Phase A
2 - #6-250 kcmil
22.6 (200)
1/4" Hex
E10
Phase B
2 - #6-250 kcmil
22.6 (200)
1/4" Hex
E11
Phase C
2 - #6-250 kcmil
22.6 (200)
1/4" Hex
DC Input from Battery
E4
Battery (+)
4 - #6-250 kcmil
22.6 (200)
1/4" Hex
E5
Battery (-)
4 - #6-250 kcmil
22.6 (200)
1/4" Hex
Customer Ground
Ground
Ground
6 - #14-1/0
5.1 (45)
Slotted
NOTE
Customer ground, sized in accordance with NEC Table 250.122, can be run in any conduit listed in