54
Eaton 93PM UPS 480V Three-Wire – 100 kW Frame Installation and Operation Manual 164000227—Rev 07
Figure 25. Wire Tie Anchors
Wire Tie Anchors
Table 13. Building Alarm Connections and Wire Terminations
Terminal
Name
Description
Recommended
Wire Size
Size of
Pressure
Termination
Tightening
Torque
10
Building Alarm 1
Input: Programmable UPS
alarm, activated by a remote
dry contact closure
Twisted
Pair Wires
#18 AWG
#14-#30 AWG
2 lb in
(0.22-0.25 Nm)
9
Building Alarm 1
Return
8
Building Alarm 2
7
Building Alarm 2
Return
6
Building Alarm 3
5
Building Alarm 3
Return
4
Building Alarm 4
3
Building Alarm 4
Return
2
Building Alarm 5
1
Building Alarm 5
Return