34
Eaton 93PM UPS 480V Three-Wire – 100 kW Frame Installation and Operation Manual 164000227—Rev 07
Table 10. Recommended Output Circuit Breaker Ratings (Continued)
Output Rating
UPS Model
UPS Rating
Load Rating
480V
Eaton 93PM-100-2
Eaton 93PM-100-3 (N+1)
80 kW
80% Rated
125A
100% Rated
100A
Eaton 93PM-100-2
Eaton 93PM-100-3 (N+1)
90 kW
80% Rated
150A
100% Rated
110A
Eaton 93PM-100-2
Eaton 93PM-100-3 (N+1)
100 kW
80% Rated
150A
100% Rated
125A
There is no manual DC disconnect device within the UPS.
Battery voltage is computed at 2 volts per cell as defined by Article 480 of the NEC. Rated battery current is
computed based on 2 volts per cell.
If required, external DC input overcurrent protection and disconnect switch is to be supplied by the customer.
and
list the recommended ratings for circuit breakers satisfying the criteria for each battery
voltage. Recommended disconnect size is based on a maximum full load discharge time less than 3 hours. For
longer discharge times a larger disconnect may be required.
Table 11. Recommended DC Input Battery Disconnect Circuit Breaker Ratings (216 Cell)
Output Rating
UPS Model
UPS Rating
432V
Eaton 93PM-100-1
Eaton 93PM-100-2 (N+1)
20 kW
60A
Eaton 93PM-100-1
Eaton 93PM-100-2 (N+1)
30 kW
90A
Eaton 93PM-100-1
Eaton 93PM-100-2 (N+1)
40 kW
125A
Eaton 93PM-100-1
Eaton 93PM-100-2 (N+1)
50 kW
150A
Eaton 93PM-100-2
Eaton 93PM-100-3 (N+1)
60 kW
200A
Eaton 93PM-100-2
Eaton 93PM-100-3 (N+1)
70 kW
225A
Eaton 93PM-100-2
Eaton 93PM-100-3 (N+1)
80 kW
250A
Eaton 93PM-100-2
Eaton 93PM-100-3 (N+1)
90 kW
300A
Eaton 93PM-100-2
Eaton 93PM-100-3 (N+1)
100 kW
300A