225A and 400A distribution panels use Cutler-Hammer bolt-on type BAB or QBHW breakers. Breakers are
to be provided by the customer.
•
Material and labor for external wiring recommendations are to be provided by the customer.
•
Refer to the appropriate Eaton 93PM UPS installation and operation manual listed in paragraph
for UPS cabinet conduit and terminal specifications and locations.
•
The term
line-up-and-match
refers to accessory cabinets that are physically located adjacent to the UPS.
The term
standalone
refers to accessory cabinets that are located separate from the UPS.
33..22..33
220088V
V//220088V
V IIA
AC
C--D
D P
Poow
weerr W
Wiirriinngg P
Prreeppaarraattiioonn w
wiitthh M
Maaiinntteennaannccee B
Byyppaassss
Read and understand the following information in addition to the information in paragraph
IAC-D Power Wiring Preparation
while planning and performing a system installation with a single-feed
UPS and a Sidecar Integrated Accessory Cabinet-Bypass (SIAC-B) or wall mount maintenance bypass:
NOTE
The 208V/208V IAC-D can be used only with a three-breaker SIAC-B or wall mount
maintenance bypass.
•
The SIAC-B maintenance bypass input (E6,E7,E8) or wall mount maintenance bypass input must be fed
from the output of the 208V/480V IAC-D input autotransformer for single-feed systems when using a
three-breaker bypass. This must be a 480V feed.
•
The 480V output of the UPS (E9, E10, and E11) is wired to the SIAC-B or wall mount maintenance bypass
MIS input.
•
The 480V output from the SIAC-B (E9, E10, and E11) or wall mount maintenance bypass is wired to the
480V input of IAC-D.
For external input power wiring recommendations, including the minimum AWG size of external wiring, see
for 480V/208V IAC-D and
for 208V/208V IAC-D. Wire sizes listed are for copper wiring only.
Table 4. External Input Power Wiring Recommendations for the Eaton 93PM IAC-D (480V/208V)
Basic Unit Rating
Units
Ratings
kW
50
100
150
200
Input Voltage
Volts
480
480
480
480
480 VAC Input to IAC-D from UPS
(3) Phases, (1) Ground
A
Maximum Amps
60
120
180
240
Minimum Conductor Size (Phase A,
B, and C)
Number per Phase
AWG or kcmil
(each)
3
(1)
2/0
(1)
2/0
(2)
2/0
(2)
Minimum Conductor Size (Ground)
Number
—
AWG or kcmil
(each)
8
(1)
6
(1)
4
(2)
1
(1)
NOTE
Callout letter
A
maps to the Oneline Schematics detailed in
.