Eaton 93PM Integrated Accessory Cabinet-Distribution (50–200 kW) Installation and Operation Manual P-164000229—Rev 09
5
•
100 kW IAC-D with 480/208 Vac output transformer and:
–
Up to two PRL1A 225A 42-pole distribution panels.
–
One PRL1A 225A 42-pole distribution panel and up to three JG-Frame 3-pole 100-250A adjustable
subfeed distribution breakers.
–
Up to five JG-Frame 3-pole 100-250A adjustable subfeed distribution breakers.
–
One LG-Frame 3-pole 350A output breaker.
•
100 kW IAC-D with 208/480 input transformer, 480/208 Vac output transformer and:
–
One PRL1A 225A 42-pole distribution panel.
–
One PRL1A 225A 42-pole distribution panel and up to three JG-Frame 3-pole 100-250A adjustable
subfeed distribution breakers.
–
Up to five JG-Frame 3-pole 100-250A adjustable subfeed distribution breakers.
–
One LG-Frame 3-pole 350A output breaker.
•
150 kW IAC-D with 480/208 Vac output transformer and:
–
Up to two PRL1A 225A 42-pole distribution panels.
–
Up to two PRL1A 225A 42-pole distribution panels and one FD-Frame 3-pole 225A subfeed
distribution breaker.
–
One PRL1A 225A 42-pole distribution panel and one PRL1A 400A 42-pole branch distribution panel.
–
One PRL1A 225A 42-pole distribution panel, one PRL1A 400A 42-pole branch distribution panel, and
one FD-Frame 3-pole 225A subfeed distribution breaker.
–
One PRL1A 225A 42-pole distribution panel and up to three JG-Frame 3-pole 100-250A adjustable
subfeed distribution breakers.
–
Up to five JG-Frame 3-pole 100-250A adjustable subfeed distribution breakers.
–
One LG-Frame 3-pole 600A output breaker.
•
200 kW IAC-D with 480/208 Vac output transformer and:
–
Up to two PRL1A 225A 42-pole distribution panels.
–
Up to two PRL1A 225A 42-pole distribution panels and one FD-Frame 3-pole 225A subfeed
distribution breaker.
–
One PRL1A 225A 42-pole distribution panel and one PRL1A 400A 42-pole branch distribution panel.
–
One PRL1A 225A 42-pole distribution panel, one PRL1A 400A 42-pole branch distribution panel, and
one FD-Frame 3-pole 225A subfeed distribution breaker.
–
One PRL1A 225A 42-pole distribution panel and up to three JG-Frame 3-pole 100-250A adjustable
subfeed distribution breakers.
–
Up to five JG-Frame 3-pole 100-250A adjustable subfeed distribution breakers.
–
One MD-Frame 3-pole 700A output breaker.
Summary of Contents for 93PM IAC-D