Eaton 93PM Integrated Accessory Cabinet-Distribution (50–200 kW) Installation and Operation Manual P-164000229—Rev 09
59
Figure 33. Output Breaker Output Power Terminal Detail – 150 kW and 200 kW
AC Output to
Critical Load
Phase A
Phase C
Phase B
Neutral
44..44
A
Addjjuussttaabbllee S
Suubbffeeeedd B
Brreeaakkeerrss
The JG-Frame subfeed breakers installed in the IAC-D contain adjustable current trip settings. The continuous
current (Ir) values for the corresponding lettered adjustment setting marked on the subfeed breakers are listed
in
.
To adjust breaker:
1.
If not already open, open the front door (see
) by lifting the latch from the bottom and turning to
the right (counterclockwise) and swing the door open.
2.
Loosen the screws securing the inside distribution panel door and swing the door open.
3.
Loosen the screws securing the inside trim plate(s) and remove the plate(s). Retain trim plate(s) and
hardware for later use.