Conduit sizes listed are for copper wiring only.
Battery Conductor Routing
External overcurrent protection and disconnect are not provided by this product, but are required by codes.
Refer to Table 3-4 for wiring requirements. If an output lockable disconnect is required, it is to be supplied by
the customer.
Table 3-10. 480V Power Cable Conduit Recommendations
UPS Model
Voltage
Terminal
Number of Wires
in Conduit
Minimum Conduit
Trade Size
Number of
Conduits
Eaton 9395C-1000/1000
Eaton 9395C-1000/1100
480 Vac
AC Input to UPS Rectifier
(A, B, C, Ground)
4
3
5
AC Input to Bypass and Output
(A, B, C, Ground)
4
3
5
DC
(Common Battery)
Battery
(Positive, Negative, Ground)
5
3.5
5
Eaton 9395C-1100/1100
480 Vac
AC Input to UPS Rectifier
(A, B, C, Ground)
4
3
6
AC Input to Bypass and Output
(A, B, C, Ground)
4
3
5
DC
(Common Battery)
Battery
(Positive, Negative, Ground)
7
4
4