Installing Options and Accessories
5-2
Eaton
®
Power Xpert
®
9395C UPS Installation and Operation Manual P-164000821—Rev 01
www.eaton.com/powerquality
5.1
Installing an Optional Powerware Hot Sync CAN Bridge Card
As an option, a Powerware Hot Sync Controller Area Network (CAN) Bridge Card, shown in Figure 5-1, can be
installed to provide connectivity for operational mode control of a parallel system. In addition, this card can be
used to connect optional system monitoring devices, such as a Remote Monitor Panel II, a Relay Interface
Module II, or a Supervisory Contact Module II to the UPS.
Figure 5-1. Powerware Hot Sync CAN Bridge Card
To install the card:
1.
Verify the UPS system is turned off and all power sources are removed. See Chapter 7, “UPS Operating
Instructions” for shutdown instructions.
2.
Unfasten the front door latch and swing the door open (see Figure 4-1).
3.
Install the Powerware Hot Sync CAN Bridge Card into an open X-Slot communication bay on the front of
the UPS. See Figure 4-18 and Figure 4-23 for X-Slot communication bay locations.
NOTE
Only one Powerware Hot Sync CAN Bridge Card can be installed in the UPS.
Multiple CAN cards are not supported and will cause system conflicts.
Plug-in Terminal
Block J3