Installation
Eaton
®
Power Xpert
®
9395C UPS Installation and Operation Manual P-164000821—Rev 01
www.eaton.com/powerquality
4-27
Figure 4-19. Interface Terminal Detail
Figure 4-20. Typical Alarm Relay Connection
X-Slot Communication Bays
TB1
TB2
See Figure 4
‐
23
for terminal
assignments.
TB2
NOTE
Alarm relay contacts have a maximum current rating of 5A and a switched voltage rating of 30 Vac and 28 Vdc.
NOTE
Alarm relay normally-open and normally-closed return terminals are separated on the terminal board but are electrically in comm
NOTE
Do not directly connect relay contacts to the mains related circuits. Reinforced insulation to the mains is required.
NOTE
Alarm relay wiring should be a minimum of 22 AWG.
Alarm Relay
3
4
5
6
Alarm Relay NC
Alarm Relay Common
Alarm Relay NO
Alarm Relay Common
Summary of Contents for 9395C-1000/1000