GT200 series general purpose inverter instruction manual
Parameter
code
Parameter
name
Setting range
Mini
munit
Default
value
Mod
ition
F2.01
Start frequency
0.20
~
60.00Hz
0.01Hz
0.50Hz
○
F2.02
Start frequency
retention time
0.0
~
10.0s
0.1s
0.0s
○
F2.03
Start DC braking
current
0.0~100.0% frequency inverter
rated currency
0.1%
80.0%
○
F2.04
Start DC braking
time
0.0 (no action)
0.1~30.0s
0.1s
0.0s
○
F2.05
Acceleration and
deceleration
mode selection
0
:
Straight line acceleration and
deceleration
1
:
S curve acceleration and
deceleration
1
0
×
F2.06
Reserved
○
F2.07
Reserved
○
F2.08
Stop mode
0
:
Decelerate to stop
1
:
Coast to stop
2
:
Stop decelDC
braking
3
:
Positioning deceleration
stop+DC braking
1
0
×
F2.09
Stop DC braking
start frequency
0.00
~
60.00Hz
0.01Hz
0.00Hz
○
F2.10
Stop DC braking
waiting time
0.00
~
10.00s
0.01s
0.00s
○
F2.11
Stop DC braking
current
0.0
~
100.0% frequency
converter rated current
0.1%
80.0%
○
F2.12
Stop DC braking
time
0.0 (no action)
0.1
~
60.0s
0.1s
0.0s
○
F2.13
Revolving speed
tracking speed
1~100
1
30
*
F2.14
Acceleration time
2
0.1
~
3600
Note
:
default unit second; refer
to FC.09 for units of
acceleration and deceleration
time selection
0.1
Model
determined
○
F2.15
Deceleration time
2
0.1
○
F2.16
Acceleration time
3
0.1
○
F2.17
Deceleration time
3
0.1
○
F2.18
Acceleration time
4
0.1
○
36