GT200 series general purpose inverter instruction manual
Fb.01
Communicatio
n configuration
LED units digit
:
Baud rate selection
0
:
1200BPS
1
:
2400BPS
2
:
4800BPS
3
:
9600BPS
4
:
19200BPS
5
:
38400BPS
LED tens digit
:
data format
0
:
1-8-2-N format, RTU
1
:
1-8-1-E format, RTU
2
:
1-8-1-O format, RTU
3
:
1-7-2-N format, ASCII
4
:
1-7-1-E format, ASCII
5
:
1-7-1-O format, ASCII
6
:
1-8-1-N format,RTU
LED hundreds digit
:
analog input
terminal
0
:
Ineffective
1
:
Effective
1
0003
×
Fb.02
Reserved
-
-
0
*
Fb.03
Local response
delay
0
~
1000mS
1
5ms
×
Fb.04
Communicatio
n overtime
detection time
0.0
~
1000s
0.1
0.0s
×
Fb.05
Host routing
00~11
0
11
×
Fb.06
Linkage ratio
setting
0.01~10.00
0.01
1.00
○
Advanced function parameter FC group
FC.00
Dynamic
braking
selection
0~2
1
1
×
FC.01
Braking usage
rate
0~5
1
3
×
FC.02
AVR function
0
:
No action
1
:
Action all the time
2
:
No action only in deceleration
1
2
×
67