GT200 series general purpose inverter instruction manual
FA.09
Automatic
reset times
0
~
10,0 shows no automatic reset
function
Note
:
Module protection and
external device fault has no reset
function.
1
0
×
FA.10
Automatic
reset interval
time
2.0
~
20.0s
0.1s
5.0s
×
FA.11
Overload
pre-alarm
detection
setting
LED units digit
:
Action selection
0
:
Detecting all the time
1
:
Detect only in constant speed
LED tens digit
:
Alarming selection
0
:
No alarming, continue to run
1
:
Alarm, halt
LED hundreds digit
:
Detection
quantity selection
0
:
Relative to motor rated
current
(
E008
)
1
:
Relative to frequency
converter rated current
(
E009
)
1
000
×
FA.12
Overload
pre-alarm
detection level
20.0%
~
200.0%
0.1%
130.0%
×
FA.13
Overload
pre-alarm
detection time
0.0
~
60.0s
0.1s
5.0s
×
64