GT200 series general purpose inverter instruction manual
Address
Function Code
Register
Address
Register
Content
Checksum
0x05
0x06
0x3200
0x00D0
0x876A
0x05
0x06
0x3200
0x00D0
0x876A
5#inverter Jog stops:
Address
Function Code
Register
Address
Register
Content
Checksum
0x05
0x06
0x3200
0x00C0
0x86A6
0x05
0x06
0x3200
0x00C0
0x86A6
5# inverter fault resets:
Address
Function Code
Register
Address
Register
Content
Checksum
0x05
0x06
0x3200
0x0280
0x86C6
0x05
0x06
0x3200
0x0280
0x86C6
Read 4#inverter’s running frequency, and inverter response running frequency is
50.00HZ:
Address
Function
Code
Register
Address
Register
Number or
Read Bytes
Register
Content
Checksum
0x04
0x03
0x3301
0x0001
None
0xDADB
0x04
0x03
None
0x02
0x1388
0x7912
Read 4#inverter’s running frequency, and inverter response running frequency is
50.00HZ.
Address
Function
Code
Register
Address
Register
Number or
Read Bytes
Register
Content
Checksum
0x04
0x03
0x3301
0x0001
None
0xDADB
0x04
0x03
None
0x02
0x1388
0x7912
Modify 5#inverter’s accelerating time 1 (which is function code F0.10) is 10.0s, which
does not save after power off.
Address
Function
Code
Register
Address
Register Content
Checksum
0x05
0x06
0x000A
0x0064
0xA9A7
0x05
0x06
0x000A
0x0064
0xA9A7
Read 5#inverter’s output current, and inverter response output current is 30.0A.
103