GFL-Series User Manual V1.1
15
www.eepowersolutions.com | Tel: 1-877-805-3377 | Fax: 1-414-962-3660 | [email protected] | V1.1
Figure 4-7 Signal Receiver Starting Screen
4.3.1 Setting the Frequency and Audio Indicator.
The screen shown in Figure 4-8 appears when
GND-Fault
is selected in the previous
screen. The receiver frequency is fixed at 10Hz, so this cannot be changed
An audio indicator can be set to assist fault tracing. The level at which the audio sounds
a ‘beep’ is set in the location setting screen (Figure 4-8),
If, for example, the Audio indicator is set to 4, the ‘beep’ will sound if a value above 40%
of the reference value is detected. This can be useful during fault tracing. Set the audio
values based on experience with the circuit under test, or begin with a value such as 4.
Once the Audio value has been set, selecting
OK
on the screen in Figure 4-8.