![background image](http://html1.mh-extra.com/html/eagle-eye-power-solutions/gfl-1000/gfl-1000_user-manual_3284128014.webp)
GFL-Series User Manual V1.1
13
www.eepowersolutions.com | Tel: 1-877-805-3377 | Fax: 1-414-962-3660 | [email protected] | V1.1
detection systems are present, set the current limit to
UL
, which will in any case limit the
output power to about 5W or 40mA, whichever is less.
Select
Next
to continue. The signal generator will operate and a screen similar to that
shown in Figure 4-5 will appear. The generator will briefly produce an output in order to
measure the system impedance.
Figure 4-5 Signal Generator Initial Output
The display shows the signal generator voltage and current waveforms, together with
calculated values of fault current, resistance and leakage capacitance.
Press
Cont
. The screen shown in Figure 4-4 will be shown again.
The output voltage may have been reduced automatically to limit the output current. If
the output current is too low, the output voltage may have been increased.