ATC770 Microprocessor-Based Pressure/Process Controller
79
Range:
Use
▲
and
▼
keys to switch the upper display from OFF to On 4, then press FUNC
key to load the default data of the parameters belonging to group 1, group 2, group
3 and group 4.
11.5
G
ROUP
5 P
ARAMETERS
PRESSURE INPUT SELECTION - Group 5
Available:
Always.
Upper display: Type of pressure input selection.
Lower display: PI.TYP
Range:
Str, 0-20, 4-20, 0-5, 0-10. Strain gage, 0-20 mA, 4-20 mA, 0-5V, 0-10V
Default value:
Strain gage.
NOTE: Remember to make the proper selection of internal jumpers.
REMOTE SET POINT INPUT SELECTION - Group 5
Available:
Only if remote set point input circuit is fitted.
Upper display: Type of remote set point input circuit is fitted.
Lower display: RI.TYP
Range:
OFF, 0-20, 4-20, 0-10. Disabled, 0-20 mA, 4-20 mA, 0-10V.
Default value:
4-20 mA.
NOTE: Remember to make the proper selection of internal jumpers.
CONTROL OUTPUT SELECTION - Group 5
Available:
Always.
Upper display: Type of control output selection.
Lower display: CO.TYP
Range:
0-20, 4-20, 0-10, -10-10, 0-5. 0-20 mA, 4-20 mA, 0-10V, -10-10V, 0-5V
Default value:
0-10V.
NOTE: Remember to make the proper selection of internal jumpers.
RETRANSMISSION OUTPUT SELECTION - Group 5
Available:
Only if retransmission output circuit is fitted.
Upper display: Type of retransmission output selection.
Lower display: OFF, 0-20, 4-20, 0-10, -10-10, 0-5. Disabled, 0-20 mA, 4-20 mA, 0-10V, -10-10V,
0-5V.
Default value:
0-10V.
NOTE: Remember to make the proper selection of internal jumpers.
Summary of Contents for ATC770
Page 19: ...ATC770 Microprocessor Based Pressure Process Controller 19 Fig 2 ATC770 Outline Drawing...
Page 23: ......
Page 30: ...30 Fig 6 Remote Set Point Jumper Location Board E...
Page 84: ...NOTES...
Page 85: ...NOTES...
Page 86: ...NOTES...
Page 88: ...DYNISCO INSTRUMENTS 38 FORGE PARKWAY FRANKLIN MA 02038 ATTN MARKETING DEPT Place Stamp Here...