4
2.
W
IRING
•
Connect the wires from transducer cable as shown in the terminal diagram.
•
Connect final control device.
•
Connect alarm(s) if applicable. Note that alarm defaults are High, Reverse Acting for alarms 2 &
3 - alarm 1 is low inhibited.
•
Connect power to the appropriate terminals as shown.
3.
S
CALING
•
Apply power to the instrument; Upper display will give a reading near zero.
•
Lower display will read the manual output %.
•
Press FUNC key until the Upper display reads NONE and lower display reads GROUP.
•
If your transducer is not a 10,000-psi model, select Group 3 using the Up arrow, enter with
function key.
•
Lower display reads PI.FSV (Full Scale Value), and the upper display reads 10,000. NOTE: If
your transducer is a 10,000-psi model skip next two steps. Scroll to GROUP and select 2.
•
Using the Down arrow key set the appropriate Full Scale Value for your transducer.
•
Enter using the FUNC key to scroll until GROUP legend appears again.
•
Using Up arrow key, select GROUP 2. Enter with FUNC key.
•
Follow instructions for Calibration and Operation in Step 4 of Quick Start
4.
C
ALIBRATION
AND
O
PERATION
•
Lower display reads ZERO.C and upper display reads OFF. Be sure transducer is at operation
temperature and that no pressure is applied.
•
Change upper display to ON by using the Up arrow key. Enter with the FUNC key. After a few
seconds, the lower display will show SPAN.C and upper display will show OFF.
•
Change upper display to ON using Up arrow key. Enter with the FUNC key. In a few seconds
lower display shows SMART and upper display shows OFF. Calibration is complete.
•
Using the FUNC key, scroll to the GROUP display. Enter 1 with the Up arrow, and enter with
the FUNC key. Instrument shows 0 on upper display and SP on lower display.
•
Set Process Setpoint. Press Function twice.
•
Set Alarm 1,2,3 thresholds (if applicable).
•
Press FUNC twice. Lower display will read GROUP, and upper display will read none.
•
Press FUNC key. Upper display will read 0 +/- 10 process pressure, lower display will read 0.
This is control output %.
•
Be sure process is at operating temperature.
•
Utilizing up and down keys, manipulate the output % until the upper display is reading at
approximately the setpoint.
•
Press FUNC key until lower display reads GROUP. Select group 2.
•
Press function key three times. Lower display reads SMART and upper display reads OFF.
•
Using up arrow key, turn SMART function to on. Enter with FUNC key.
•
SMART LED will flash and a countdown will begin as the controller arrives at initial P&I(D)
parameters.
Summary of Contents for ATC770
Page 19: ...ATC770 Microprocessor Based Pressure Process Controller 19 Fig 2 ATC770 Outline Drawing...
Page 23: ......
Page 30: ...30 Fig 6 Remote Set Point Jumper Location Board E...
Page 84: ...NOTES...
Page 85: ...NOTES...
Page 86: ...NOTES...
Page 88: ...DYNISCO INSTRUMENTS 38 FORGE PARKWAY FRANKLIN MA 02038 ATTN MARKETING DEPT Place Stamp Here...