ATC770 Microprocessor-Based Pressure/Process Controller
71
Default value:
Process alarm.
ALARM 1 TYPE - Group 3
Available:
Only if A1.LNK is different than OFF.
Upper display: Selection of alarm 1 type.
Lower display: A1.TYP
Range:
HI, LO, InhIb. High, low, low with mask at start-up. For band alarm high means
outside band alarm, while low means inside band alarm.
Default value:
Low with mask at start-up.
ALARM 2 INPUT CHANNEL LINK - Group 3
Available:
Always.
Upper display: Configuration for alarm 2 selection.
Lower display: A2.LNK
Range:
OFF, ProC, band, deu. Disabled, process alarm, band alarm, deviation alarm.
Default value:
Process alarm.
ALARM 2 TYPE - Group 3
Available:
Only if A2.LNK is different from OFF.
Upper display: Selection of alarm 2 type.
Lower display: A2.TYP
Range:
HI, LO, InhIb. High, low, low with mask at start-up. For band alarm high means
outside band alarm, while low means inside band alarm.
Default value:
High.
ALARM 3 INPUT CHANNEL LINK - Group 3
Available:
Only if Alarm 3 output is fitted.
Upper display: Configuration for alarm 3 selection.
Lower display: A3.LNK
Range:
OFF, ProC, band, deu. Disabled, process alarm, band alarm, deviation alarm.
Default value:
Process alarm.
ALARM 3 TYPE - Group 3
Available:
Only if A3.LNK is different than OFF.
Upper display: Selection of alarm 3 type.
Lower display: A3.TYP
Range:
HI, LO, InhIb. High, low, low with mask start-up. For band alarm high means
outside band alarm, while low means inside band alarm.
Default value:
High.
Summary of Contents for ATC770
Page 19: ...ATC770 Microprocessor Based Pressure Process Controller 19 Fig 2 ATC770 Outline Drawing...
Page 23: ......
Page 30: ...30 Fig 6 Remote Set Point Jumper Location Board E...
Page 84: ...NOTES...
Page 85: ...NOTES...
Page 86: ...NOTES...
Page 88: ...DYNISCO INSTRUMENTS 38 FORGE PARKWAY FRANKLIN MA 02038 ATTN MARKETING DEPT Place Stamp Here...