ATC770 Microprocessor-Based Pressure/Process Controller
35
Fig. 9
Input Selection J84 for Amplified Input
6.1.4 S
ETTING
THE
P
RIMARY
I
NPUT
F
ULL
-S
CALE
V
ALUE
The model number of the transducer or transmitter will designate the full-scale pressure capability.
For example, model number TPT432A-5M-6/18 indicates that the full-scale pressure is 5,000 (5M),
while the PT150-5C indicates that the full-scale pressure is 500 (5C). Since the default value in the
instrument is 10,000 full scale, the input full scale value must be changed to 5,000 (or 500). Note
that there are no units here, it can be psi, bar, mPa, kg/cm2 or any engineering unit; the magnitude
is all that is important.
To set the full-scale value, press the
FUNC
key until
nonE and GROUP show on the display. Press
the
▲
key until
3 shows in the upper display. Press the
FUNC
key and the upper display will show
10000 while the lower display shows PI.FSV. Hold the
▲
or
▼
key until the upper display changes
to
5000 (or whatever the full-scale value of the primary input may be). Press the
FUNC
key to set
the value. Check that the next display reads
0 in the upper display and PI.LSV in the lower display; if
not, set to zero with the arrow keys and press
FUNC
to lock in the value. Finally, press the
A/M
key
to go back to the active display. Similarly, if the full-scale pressure is 350 Bar (3.5CB), set
PI.FSV to
350.
Summary of Contents for ATC770
Page 19: ...ATC770 Microprocessor Based Pressure Process Controller 19 Fig 2 ATC770 Outline Drawing...
Page 23: ......
Page 30: ...30 Fig 6 Remote Set Point Jumper Location Board E...
Page 84: ...NOTES...
Page 85: ...NOTES...
Page 86: ...NOTES...
Page 88: ...DYNISCO INSTRUMENTS 38 FORGE PARKWAY FRANKLIN MA 02038 ATTN MARKETING DEPT Place Stamp Here...