K100-C
Dec’15
- 28 -
Trouble Shooting Guide (cont’d)
Condition:
Cause:
Suggested Correction:
E. Intake Valve Leaks Oil
When Unit Stops.
Intake Valve Seal leaks.
Intake Valve stuck in open position or 3 Way
Solenoid not working properly.
2 Way Solenoid not functioning.
Repair using an Intake Valve Repair Kit.
Repair or replace the Intake Valve or 3 Way
Solenoid.
Replace the 2 Way Solenoid.
F. Oil Consumption is Too
High.
1. Oil level is too high.
2. Oil Return Line (Scavenge Line) is blocked.
3. Oil Separator is saturated with oil.
4. Wrong type of oil used.
5. Unit is operating at too high a temperature.
6. Oil leak.
7. Unit load is light or excessive load/idle
cycles.
1. Reduce the oil level to the proper level.
2. Clean and/or replace the Scavenge In-Line
Filter.
3. Replace the Oil Separator.
4. Change to factory recommended oil.
5. See ‘Section C’.
6. Repair oil leak.
7. Ensure Unit is set to operate at correct
pressures, and there is a minimum of 10 psi
differential. Also the Unit could be oversized for
the tank capacity.
G. Compressor Surges.
1. Restriction in Heat Exchanger or Hoses.
2. Pressure Transducer setting is incorrect or
malfunctioning.
3. Blockage at Unit outlet.
4. If present, the Dryer is freezing up, not
allowing air to pass through.
5. Air Receiver is too small.
1. Flush out or replace.
2. Set pressure as per instructions or replace.
3. Check for obstructions in outlet piping.
4. Check that the Dryer parameters are correct.
Increase dew point to 2.0 if required.
5. Use a minimum 400 Gallon Tank.
H. High Power Consumption.
1. Improper air pressure settings.
2. Solenoid is not functioning.
3. The voltage in the building is too low or
there is a phase imbalance.
4. The Motor is failing.
1. Reset the pressure as per factory defaults.
2. Inspect or replace as necessary.
3. Contact an Electrician to verify.
4. Have Motor inspected.
I Fault Alarms.
1. Emergency Stop.
2. High Temperature.
3. Low Temperature.
4. High pressure.
1. Ensure Emergency Stop Button is not pressed
in.
2. See ‘Section C’.
3. Ambient temperature is too low. Increase to
10°C (50°F).
Check the pressure settings, the Pressure
Transducer and the wiring to the Transducer.