K100-C
Dec’15
- 18 -
Compressor Storage
At times, it may become necessary to store a Compressor Unit for an extended period of time, this because a) the
site may not be ready, b) the Unit may be shipped overseas, or c) the Unit may not be required for a period of
time (seasonal applications, etc). When storing a Compressor, the following areas must be addressed:
Location of the Unit.
The Unit must be stored in a cool, dry place away from the elements.
The Unit cannot be exposed to frost. Frost will damage the Seals, Tubing, etc.
The Unit cannot be exposed to moisture and condensation. Moisture will lead to component corrosion,
and will affect electrical components.
Temporary De-commissioning of the Unit.
If the Unit is not required for a short period of time, and is installed in its permanent location during that time:
Run the Unit for 30 minutes under load every week. This should prevent any corrosion.
Check the oil level before running.
Long Term De-commissioning of the Unit.
If the Unit is not required for a longer period of time, and is installed in its permanent location during that time:
Run the Unit for a minimum of 30 minutes under load before shutting down.
Switch the Unit off and allow for adequate ventilation in the room.
Turn off and lock the main power supply to the Unit.
Allow the Unit to cool down fully.
Disconnect the air and electrical connections to the Unit.
Remove drive motor fuses in order to prevent accidental start-up
If possible, the placement of desiccant inside the Unit Cabinet will assist in limiting moisture in the Unit.
Regularly turn the compressor’s drive shaft manually in order to prevent damage due to lack of use
Re-commissioning of the Unit.
If the Unit has been stored for a short period of time and has been run on a weekly basis, as suggested in
‘Temporary De-Commissioning of the Unit’ above, check to ensure that the oil level is correct. Once completed,
the Unit should be ready for normal use.
If stored for a longer period of time as noted in ‘Long Term De-Commissioning of the Unit’ above:
Reconnect the air and electrical connections to the Unit.
Remove any desiccant that was previously placed inside the Unit Cabinet.
Complete the ‘Start-up Procedures’ as noted on Page 15 of this manual.
If you have any questions concerning any of the above items or require
assistance, please contact your local DV Systems Distributor or Service
Center.