7.11 Controller (
Controller settings
)
The pumps have a factory default setting of gain (K
p
) and integral
time (T
i
).
However, if the factory setting is not the optimum setting, you can
change the gain and the integral time:
• Set the gain (K
p
) within the range from 0.1 to 20.
• Set the integral-action time (T
i
) within the range from 0.1 to
3600 s.
If you select 3600 s is, the controller will function as a P
controller.
Furthermore, you can set the controller to inverse control.
This means that if you increase the setpoint, the speed will be
reduced. In the case of inverse control, you must set the gain (K
p
)
within the range from -0.1 to -20.
Guidelines for setting of PI controller
The tables below show the recommended controller settings:
L1 = Distance [m] between pump and sensor.
1)
In heating systems, an increase in pump performance will
result in a rise in temperature at the sensor.
2)
In cooling systems, an increase in pump performance will
result in a drop in temperature at the sensor.
L2 = Distance [m] between heat exchanger and sensor.
L2 = Distance [m] between heat exchanger and sensor.
General rules of thumb
If the controller is too slow-reacting, increase K
p
.
If the controller is hunting or unstable, dampen the system by
reducing K
p
or increasing T
i
.
Factory setting
See section
Pump variant
Controller
(Controller settings)
CME
●
CRE, CRIE, CRNE, SPKE, MTRE
●
Constant differential
pressure
K
p
T
i
0.5
0.5
0.5
L1 < 5 m: 0.5
L1 > 5 m: 3
L1 > 10 m: 5
Constant
temperature
K
p
T
i
Heating
system
1)
Cooling
system
2)
0.5
-0.5
10 + 5L2
0.5
-0.5
30 + 5L2
p
p
p
p
ǻS
L1
L1
ǻS
L2
t
L2
t
Constant differential
temperature
K
p
T
i
-0.5
10 + 5L2
Constant flow rate
K
p
T
i
0.5
0.5
Constant pressure
K
p
T
i
0.5
0.5
0.5
0.5
Constant level
K
p
T
i
-2.5
100
2.5
100
t
L2
t
t
t
L2
Q
p
p
L
L
Summary of Contents for VT Booster Set
Page 1: ...VT Booster Set O M Manual...
Page 3: ...1 Important Health Safety Information Page 3 VT Booster Set...
Page 10: ...2 System Information Installation and Commissioning Page 10 VT Booster Set...
Page 11: ...2 1 Booster Set Components VT Booster Set Components Page 11 VT Booster Set...
Page 12: ...2 2 Control Panel Wiring Diagrams Twin Pump Wiring Diagram Single Phase Page 12 VT Booster Set...
Page 13: ...Twin Pump Wiring Diagram 3 Phase Page 13 VT Booster Set...
Page 15: ...VR VASCO Cold Water Booster Sets Page 15 VT Booster Set...
Page 16: ...VT3 Three Phase Control Panel Wiring Diagram Page 16 VT Booster Set...
Page 17: ...Page 16a VT Booster Set...
Page 23: ...3 User Maintenance and Troubleshooting Page 22 VT Booster Set...
Page 43: ...Appendix 14...
Page 50: ...Appendix 21...
Page 51: ...Appendix 22...
Page 55: ...Appendix 26...
Page 56: ...Appendix 27...