English (GB)
12
7. Description of functions
7.1 Setpoint
You can set the setpoint for all control modes when you have
selected the desired control mode. See section
Factory setting
See section
.
7.2 Operating mode
Possible operating modes:
• Normal
The pump runs according to the selected control mode.
• Stop
The pump stops.
• Min.
You can use the minimum curve mode in periods in which a
minimum flow is required. When operating according to the
minimum curve, the pump is operating like an uncontrolled
pump.
• Max.
You can use the maximum curve mode in periods in which a
maximum flow is required. When operating according to the
maximum curve, the pump is operating like an uncontrolled
pump.
• Manual
The pump is operating at a manually set speed. In "Manual"
the setpoint via bus is over-ruled. See section
All operating modes are illustrated in fig.
.
Fig. 9
Operating modes
Factory setting
See section
.
7.3 Set manual speed
This menu is only available in the advanced control panel. With
Grundfos GO, you set the speed via the "Setpoint" menu.
You can set the pump speed in % of the maximum speed. When
you have set the operating mode to "Manual", the pump will run
at the set speed.
Factory setting
See section
.
7.4 Control mode
Possible control modes:
• Constant pressure (Const. pressure)
• Constant temperature (Const. temp.)
• Constant differential pressure (Con. diff. press.)
• Constant differential temperature (Con. diff. temp.)
• Constant flow rate (Const. flow rate)
• Constant level (Const. level)
• Constant other value (Const. other val.)
• Constant curve (Const. curve.)
Factory setting
See section
7.4.1 Constant pressure
We recommend this control mode if the pump is to deliver a
constant pressure, independently of the flow in the system. See
fig.
Fig. 10
Constant pressure
This control mode uses the factory mounted pressure sensor, if
any, which measures the discharge pressure of the pump.
For pumps without a factory mounted sensor, you must connect a
pressure sensor to one of the analog inputs of the pump. You can
set up the pressure sensor in the "Assist" menu. See section
.
Fig. 11
Constant pressure
Controller settings
For recommended controller settings, see section
.
Factory setting
See section
Pump variant
Setpoint
CME
●
CRE, CRIE, CRNE, SPKE, MTRE
●
Pump variant
Operating mode
CME
●
CRE, CRIE, CRNE, SPKE, MTRE
●
TM
06
40
24
15
15
Q
H
Q
H
Max.
Min.
Normal
Normal
Manual
Stop
Pump variant
Control mode
CME
●
CRE, CRIE, CRNE, SPKE, MTRE
●
Pump variant
Constant pressure
CME
●
CRE, CRIE, CRNE, SPKE, MTRE
●
TM
05
79
01
16
13
Examples
• One external pressure sensor.
H
Q
p
p
Summary of Contents for VT Booster Set
Page 1: ...VT Booster Set O M Manual...
Page 3: ...1 Important Health Safety Information Page 3 VT Booster Set...
Page 10: ...2 System Information Installation and Commissioning Page 10 VT Booster Set...
Page 11: ...2 1 Booster Set Components VT Booster Set Components Page 11 VT Booster Set...
Page 12: ...2 2 Control Panel Wiring Diagrams Twin Pump Wiring Diagram Single Phase Page 12 VT Booster Set...
Page 13: ...Twin Pump Wiring Diagram 3 Phase Page 13 VT Booster Set...
Page 15: ...VR VASCO Cold Water Booster Sets Page 15 VT Booster Set...
Page 16: ...VT3 Three Phase Control Panel Wiring Diagram Page 16 VT Booster Set...
Page 17: ...Page 16a VT Booster Set...
Page 23: ...3 User Maintenance and Troubleshooting Page 22 VT Booster Set...
Page 43: ...Appendix 14...
Page 50: ...Appendix 21...
Page 51: ...Appendix 22...
Page 55: ...Appendix 26...
Page 56: ...Appendix 27...