English (GB)
12
10.1.4 Fault log
For both fault types, alarm and warning, the R100 has a log
function.
Alarm log
In case of "alarm" faults, the last five alarm indications will appear
in the alarm log. "Alarm log 1" shows the latest fault, "Alarm log 2"
shows the latest fault but one, etc.
The example above gives this information:
• the alarm indication "Undervoltage"
• the fault code "(73)"
• the number of minutes the pump has been connected to the
electricity supply after the fault occurred, "8 min".
Warning log (only three-phase motors)
In case of "warning" faults, the last five warning indications will
appear in the warning log. "Warning log 1" shows the latest fault,
"Warning log 2" shows the latest fault but one, etc.
The example above gives this information:
• the warning indication "Replace motor bearings"
• the fault code "(240)"
• the number of minutes the pump has been connected to the
electricity supply since the fault occurred, "30 min".
10.2 Menu STATUS
The displays appearing in this menu are status displays only. It is
not possible to change or set values.
The displayed values are the values that applied when the last
communication between the motor and the R100 took place. If a
status value is to be updated, point the R100 at the control panel
and press "OK".
If a parameter, e.g. speed, should be called up continuously,
press "OK" constantly during the period in which the parameter in
question should be monitored.
The tolerance of the displayed value is stated under each display.
The tolerances are stated as a guide in % of the maximum values
of the parameters.
10.2.1 Display of actual setpoint
Tolerance: ± 2 %
This display shows the actual setpoint and the external setpoint
in % of the range from minimum value of sensor measuring range
to the setpoint set, see section
At a min. frequency of 8 %, a set setpoint of 67 % and an external
setpoint of 70 %, the actual setpoint will be 0.70 x (67 - 8) + 8 =
49 %
.
10.2.2 Display of operating mode
This display shows the actual operating mode (
Stop
,
Min.
,
Normal
(duty) or
Max.
). Furthermore, it shows where this operating mode
was selected (
R100
,
Motor
,
BUS
or
External
).
10.2.3 Display of actual value
The actually measured value will appear in this display if a sensor
has been connected.
10.2.4 Display of actual frequency and speed
Tolerance: ± 2 %
Tolerance: ± 5 %
This display shows the actual frequency and speed.
10.2.5 Display of input power and power consumption
Tolerance: ± 10 %
•
Power input
indicates the actual power consumption.
•
Power consumption
indicates an accumulated value which
cannot be reset.
10.2.6 Display of operating hours
Tolerance: ± 2 %
The value of operating hours is an accumulated value and cannot
be reset.
Summary of Contents for VT Booster Set
Page 1: ...VT Booster Set O M Manual...
Page 3: ...1 Important Health Safety Information Page 3 VT Booster Set...
Page 10: ...2 System Information Installation and Commissioning Page 10 VT Booster Set...
Page 11: ...2 1 Booster Set Components VT Booster Set Components Page 11 VT Booster Set...
Page 12: ...2 2 Control Panel Wiring Diagrams Twin Pump Wiring Diagram Single Phase Page 12 VT Booster Set...
Page 13: ...Twin Pump Wiring Diagram 3 Phase Page 13 VT Booster Set...
Page 15: ...VR VASCO Cold Water Booster Sets Page 15 VT Booster Set...
Page 16: ...VT3 Three Phase Control Panel Wiring Diagram Page 16 VT Booster Set...
Page 17: ...Page 16a VT Booster Set...
Page 23: ...3 User Maintenance and Troubleshooting Page 22 VT Booster Set...
Page 43: ...Appendix 14...
Page 50: ...Appendix 21...
Page 51: ...Appendix 22...
Page 55: ...Appendix 26...
Page 56: ...Appendix 27...