7.5 Analog inputs
Available inputs depending on the functional module fitted in the
pump:
* See section
13. Identification of functional module
.
In order to setup the analog input for a feedback sensor, we
recommend that you do this via the "Assisted pump setup" menu.
See section
If you wish to set up an analog input for other purposes, you can
do this manually.
You can setup the analog inputs via the "Setup, analog input"
menu. See section
If you perform the manual setting via Grundfos GO, you need to
enter the menu for the analog input under the "Settings" menu.
Function
The analog inputs can be set to these functions:
• Not active
• Feedback sensor
Sensor used for the selected control mode.
• Ext. setpoint infl.
See section
7.13 External setpoint function
• Other function.
Measured parameter
Select one of the parameters listed below, i.e. the parameter to
be measured in the system by the sensor connected to the actual
analog input. See fig.
.
Fig. 23
Overview of sensor locations
Unit
Available measuring units:
Electrical signal
Select signal type:
• 0.5 - 3.5 V
• 0-5 V
• 0-10 V
• 0-20 mA
• 4-20 mA.
Sensor range, minimum value
Set the minimum value of the connected sensor.
Sensor range, maximum value
Set the maximum value of the connected sensor.
Factory setting
See section
Function (terminal)
FM 200*
(standard)
FM 300*
(advanced)
Analog input 1, setup (4)
●
●
Analog input 2, setup (7)
●
●
Analog input 3, setup (14)
-
●
TM
06
23
28
39
14
PT
PT
PT
PT
TT
TT
TT
Q
Q
DPT
DPT
DPT
LT
LT
DPT DTT
1
5
2
4
9
10
7
12
8 16
15
3
13
6
14
11
Sensor function/measured parameter
Pos.
Inlet pressure
1
Diff. press., inlet
2
Discharge press.
3
Diff. press.,outlet
4
Diff. press.,pump
5
Press. 1, external
6
Press. 2, external
7
Diff. press., ext.
8
Storage tank level
9
Feed tank level
10
Pump flow
11
Flow, external
12
Liquid temp.
13
Temperature 1
14
Temperature 2
15
Diff. temp., ext.
16
Ambient temp.
Not shown
Other parameter
Not shown
Parameter
Possible units
Pressure
bar, m, kPa, psi, ft
Level
m, ft, in
Pump flow
m
3
/h, l/s, yd
3
/h, gpm
Liquid temperature
°C, °F
Other parameter
%
Summary of Contents for VT Booster Set
Page 1: ...VT Booster Set O M Manual...
Page 3: ...1 Important Health Safety Information Page 3 VT Booster Set...
Page 10: ...2 System Information Installation and Commissioning Page 10 VT Booster Set...
Page 11: ...2 1 Booster Set Components VT Booster Set Components Page 11 VT Booster Set...
Page 12: ...2 2 Control Panel Wiring Diagrams Twin Pump Wiring Diagram Single Phase Page 12 VT Booster Set...
Page 13: ...Twin Pump Wiring Diagram 3 Phase Page 13 VT Booster Set...
Page 15: ...VR VASCO Cold Water Booster Sets Page 15 VT Booster Set...
Page 16: ...VT3 Three Phase Control Panel Wiring Diagram Page 16 VT Booster Set...
Page 17: ...Page 16a VT Booster Set...
Page 23: ...3 User Maintenance and Troubleshooting Page 22 VT Booster Set...
Page 43: ...Appendix 14...
Page 50: ...Appendix 21...
Page 51: ...Appendix 22...
Page 55: ...Appendix 26...
Page 56: ...Appendix 27...