background image

6

HORIZONTAL INSTALLATION REQUIREMENTS

•    When venting through a sidewall, terminate the system not less than 12” 

(.3m) above the ground and above the snow line in geographical areas 

where snow accumulates.  The termination area must be kept clear of 

snow and ice at all times. See

 Figure 1.

•   Terminate the system at least 7’ (2.1m) above a public walkway or 

driveway, no less than 6’ (1.8m) from the combustion air intake of any 

appliance or 3’ (.9m) from any other building opening, gas utility meter, 

service regulator or the like. Less distance is permitted if specified in the 

appliance’s installation instructions. It also shall terminate at least 3’ (.9M) 

above any forced air inlet within 10’ (3.1m) and shall terminate at least 4’ 

(1.2m) below, 4’ horizontally from, or 1’ (.3m) above any door, window, or 

gravity air inlet into any building as provided in the National Fuel Gas Code 

ANSI Z223.1 and NFPA 54.  See

 Figure 1

.  Proper judgment may require 

greater distances depending on the side of the equipment installed or 

to allow for snow drifting or falling from falling from overhead roofs or 

trees.  The termination should be far enough away from trees, shrubs, 

or decorative items to prevent damage.

•    The total horizontal vent length from the appliance flue collar to the outside 

termination shall be in accordance with the appliance manufacturer’s 

instructions.

MVS : Maximum Vertical Spacing between Guides/Supports

MHS: Maximum Horizontal Spacing between Guides/Supports

MDE: Maximum Distance between Elbows

H: Maximum Freestanding Height above the Roof

S: Maximum Suspended Length

SUPPORT AND GUIDE SPACING FOR MODEL DS & DSLS

Inside 

diameter

MVS

MHS

MDE

H

S

Interior

Exterior

3”

10

8

12

12

10

50

4”

10

8

12

12

10

100

5”

10

8

12

12

10

100

6”

10

8

12

12

10

100

7”

10

8

12

12

10

100

8”

10

8

12

12

10

100

9”

10

8

12

12

10

100

10”

10

8

12

12

10

100

12”

10

8

12

12

10

100

14”

10

8

12

12

10

100

16”

10

8

12

12

10

100

18”

10

8

12

12

10

100

20”

10

8

12

12

10

100

22”

10

8

12

12

10

100

24”

10

8

12

12

10

100

26”

10

8

12

12

12

100

28”

10

8

12

12

12

100

30”

10

8

12

12

12

100

32”

10

8

12

12

12

100

34”

10

8

12

12

12

100

36”

10

8

12

12

12

100

Table 7: Support and Guide Spacing for Model DS & DSLS. Dimensions are in feet

SUPPORT AND GUIDE SPACING FOR MODEL DSD & DSID & DSLD

Inside 

diameter

MVS

MHS

MDE

H

S

Interior

Exterior

3”

10

8

12

12

10

50

4”

10

8

12

12

10

50

5”

10

8

12

12

10

50

6”

10

8

12

12

10

50

7”

10

8

12

12

10

50

8”

10

8

12

12

10

50

9”

10

8

12

12

10

50

10”

10

8

12

12

10

50

12”

10

8

12

12

10

50

14”

10

8

12

12

10

50

16”

10

8

12

12

10

50

18”

10

8

12

12

10

50

20”

10

8

12

12

10

50

22”

10

8

12

12

10

50

24”

10

8

12

12

10

50

26”

10

8

12

12

12

50

28”

10

8

12

12

12

50

30”

10

8

12

12

12

50

32”

10

8

12

12

12

50

34”

10

8

12

12

12

50

36”

10

8

12

12

12

50

Table 8: Support and Guide Spacing for Model DSD, DSID & DSLD.  Dimensions are in feet

7 ft above 

public 

walkways 

and drives

1 ft. above doors and windows

4 ft below any 

window or fresh air 

inlet

1 ft. above ground or 

snow line

Sidewalk

Figure 1 - Horizontal Termination Requirements

4 ft. horizontally from door 

and windows

Summary of Contents for DuraSeal DS

Page 1: ...g damage prior to installation B Proper joint assembly is essential for a safe installation Follow these instruc tions exactly as written Check severeness of joints upon completion of assembly C This...

Page 2: ...ory I II III and IV in USA UL 1738 or in Canada asType BH GasVenting as noted in ULC S636 with a maximum operating temperature of 480 F 250 C and a maximum rated positive pressure of 35 water column I...

Page 3: ...y do not overheat at points of contact Notes 1 Unenclosedrequiresatleasttwosidesopen 2 SingleWall DS DSLS maybeenclosedonlyinnon combustibleenclosure 3 Reducedclearancesmaybeattainedbyusingnon combust...

Page 4: ...bing or electrical systems Maintain rated clearances to combustibles over the entire length of the vent system DuraSeal shall not be routed into through or within any vent such as an existing masonry...

Page 5: ...25 70 6 90 90 90 45 90 45 65 7 87 5 87 5 87 5 43 75 87 5 43 75 55 8 85 85 85 42 5 85 42 5 50 9 N A N A N A N A N A N A N A 10 80 80 85 42 5 85 42 5 40 12 75 75 75 37 5 75 37 5 30 14 70 70 70 35 70 35...

Page 6: ...etween Guides Supports MDE Maximum Distance between Elbows H Maximum Freestanding Height above the Roof S Maximum Suspended Length SUPPORTANDGUIDESPACINGFORMODELDS DSLS Inside diameter MVS MHS MDE H S...

Page 7: ...ance manufacturer are permitted 4 Thetotalcontinuousdistanceoftheventsystemfromtheapplianceflue collartotheterminationshallnotexceedthatspecifiedintheappliance manufacturer sinstallationinstructions W...

Page 8: ...himble WTI OPENING DIMENSIONS FORWALL ROOF PENETRATION FOR MODEL DSID Inside Diameter WallThimble WT Wall Thimble Insulated WTI Roof Thimble RT Roof Thimble Insulated RTI 3 10x10 11x11 7x7 11x11 4 13...

Page 9: ...appliance 1 ADrainlength DL oraTeewithadrainteecap DTC isstronglyrecom mended Installthisdrainascloseaspossibletotheappliancefluecollar 2 A condensate drain is required for every 30 feet of horizontal...

Page 10: ...t SeeTable 7 8 MHS 30 Termination STA Opening dimension SeeTable 9 10 11 WallThimble WT WTI Roof Support RS Suspension Band SB Anchor Plate HD APHD Appliance Maximum distance suspended SeeTable7 8 S F...

Page 11: ...TI Maximum distance between guides SeeTable 7 8 MVS Opening dimension SeeTable 9 10 11 Minimum Clearance SeeTable 1 Maximum distance between supports SeeTable 3 4 5 6 Maximum distance between elbows w...

Page 12: ...oz 3 0 1 4 0 1 5 0 1 6 0 1 7 0 1 8 0 2 9 0 2 10 0 2 12 0 3 14 0 3 16 0 3 18 0 4 20 0 4 22 0 5 24 0 5 Table 12 Figure 9 Position of Support Important Notes DS DSD DSID ONLY 1 For Anchor Plate AP Anchor...

Page 13: ...should be used NOTE The adjustable length is a non load bearing part A support must be used after it to take the load of the sections above NOTE The inner conduit may be cut to desired length to limi...

Page 14: ...o the same chimney or vent Elbow or tee Guy support GS Centering band CB Stainless steel wire rope by other Combustible wall Masonry chimney 1 Minimum Exit cone EC Maximum distance between guides See...

Page 15: ...he Flex Flex adapter with the flexible liner 1 Before official installation 1 1 If cutting the liner on the field is required make sure the cut is square Make a marker line on both ends of the liner a...

Page 16: ...FlexVi ton caulking 2 2 Push the adapter on the liner all the way in until you can t seethe mark made on the flexible liner earlier Figure 19 Make sure that theViton caulking is sealed well at the joi...

Page 17: ...ofViton caulking at 1 2 from the edge of the flexible liner all around the inner side of it Figure 22 Figure 22 DuraSeal FlexViton caulking 3 3 Push the adapter on the liner all the way in until you...

Page 18: ...ed 2 Make sure the DuraSeal Flex is supported at the bottom of the chimney Refer to Figure 12 forguiding and support installation in the masonry chimney 3 The DuraSeal Flex liner must be installed fro...

Page 19: ...19 SECTION C SPECIFIC INFORMATION MODELS DSLS DSLD 26 TO 36 TYPICAL INSTALLATION FOR DSLS DSLD Figure 26 Typical installation for DSLD...

Page 20: ...the value In theTable 7 8 use bracing or cable guying to staballze chimney section above the roof See Figure 27 Figure 27 Height with rigid bracing or guying option for DSLS DSLD Figure 28 Maximum fre...

Page 21: ...lation add a bead of blackViton caulking over the Viton O ring NOTE Sealant Caulking is supplied by DuraVent and Individual tubes are marked Fluorodyn Caulk VITON code VITON S 2 5 oZ VITON L 11 oZ It...

Page 22: ...to the inside of the inner flue adjacent to the nipple to channel the effluent to the drain 3 The duct drain is intended for use at the end of a horizontal run where access and drainage is needed see...

Page 23: ...ged end of the tube should always point downward or towards downward slope Figure 33 Overlap Details forVariable Length INSTALLATION STEPS FORTHEVARIABLE LENGTH LV DSLS DSLD Step 1 Measure the distanc...

Page 24: ...regular length installation See JOINT ASSEMBLY section Step 8 Apply thin layer of sealant inside the retaining collar and also a continuous bead of sealant at the collar overlap seam See Figure 37 Fig...

Page 25: ...lations and must be connected to a suitable disposable point It can also be used as an access for clean outs or access purposes See Figure 41 Same installation as aTee Cap TC ELBOWS DSLS DSLD ELBOWS E...

Page 26: ...by threaded rods or from small size angles or straps are usually not satisfactory to resist bending moments due to offsets Figure 44 Maximum Spacing between supports for Offset ADAPTERS DSLS DSLD TAPE...

Page 27: ...members are supplied by the installer See Figure 48a and 48b Figure 48a Ventilated Anchor Plate on a Framework Figure 48b Detail of theVentilated Anchor Plate on a Framework Supported duct sections in...

Page 28: ...the part doesn t have any outer wall but Outer Band BSE is provided to secure the insulation on the part See Figure 51 52 53 for the three steps to install the DSLD Figure 50 Ventilated Anchor Plate...

Page 29: ...of the flange band The Heavy DutyWall Support Assembly is bolted together with provided hardware It is made with adjustable struts which allows a variable clearance from the non combustible wall to t...

Page 30: ...hardware provided to form a rigid assembly NOTE Seal joint with S 375 sealant above and below support if exposed to weather FULL ANGLE RING FAR A Full Angle Ring is used as a guide to prevent the duc...

Page 31: ...n the vertical position The inlet and outlet ends must each be supported TEE SUPPORT TheTees must be supported properly to protect them from bending It can be done by means of Anchor Plate AP Anchor P...

Page 32: ...pitch 5 to 30 See Figure 64 Figure 62 Storm Collar Figure 63 Flashing Figure 64 Adjustable Flashing NOTE The flashings are non ventilated and does not provide for any reduced clearance to combustible...

Page 33: ...tem incorporates a drain hose from either a Drain length or a Drain tee cap the hose must be inspected periodically to ensure that water is in the trap loop If a proper trap loop is not maintained exh...

Page 34: ...07 14 17 DuraVent Limited reserves the right to make changes at any time without notice in design materials specifications prices Consult your local distributor for chimney system code information 10...

Reviews: