8.7 Protection function and fault output  

 

OUT3

The protection function serves for protecting the motor 

against  destruction  e.g.  at  external  strain.  Confirma-

ble protection functions turn off the output stage when 

achieving a marginal value. This is announced by the 

fault-output OUT3. The output is performed as a PNP-

transistor 24 V-pulse switching, with a max. permissi

-

ble current strain of 12 mA. Thereby, following logic is 

essential:

/fault

Description

0

fault

1

no fault

 

For confirmation of a fault message, the motor must be 

set into status “OFF” (IN1, 2 = 0). If the cause of fault is 

debugged (e.g. switch-on voltage threshold achieved, 

temperature o.k.), this is shown via OUT3 = 1, and the 

motor can be started again.

Protection 

function

Type

Range

Confir-

mation?

Availa-

ble?

Over-tem-

perature 

of the 

electronic

Soft-

ware

85 °C off, 

70 °C on

Yes

Yes

Under-

voltage

Soft-

ware

10 V off, 

11 V on

Yes

Yes

Current 

limitation

Hard-

ware

15 A / 25 A    

standard

Yes

Blocking 

protection 

in controlled 

operation

Soft-

ware

Yes

Yes

8.7 Schutzfunktionen und Meldeausgang  

 

OUT3

Die Schutzfunktionen dienen dem Schutz des Motors 

vor  Zerstörung  z.B.  bei  extremer  Belastung.  Quittier-

bare  Schutzfunktionen  schalten  die  Endstufe  bei  Er-

reichen eines Schwellwertes ab. Dies wird durch den 

fault-Meldeausgang OUT3 angezeigt. Der Ausgang ist 

als PNP-Transistor 24 V-plusschaltend mit einer max. 

zulässigen Strombelastung von 12 mA ausgeführt.  Da-

bei gilt folgende Logik:

/fault

Bedeutung

0

Störung

1

Keine Störung

 

Zur Quittierung einer Störmeldung muss der Motor in 

den Zustand „AUS“ (IN1, 2 = 0) versetzt werden.

Ist  die  Fehlerursache  beseitigt  (z.B.  Einschaltspan-

nungsschwelle  erreicht,  Temperatur  o.k.),  wird  dies 

durch OUT3 = 1 angezeigt und der Motor kann wieder 

gestartet werden.

Schutz-

funktion

Art

Bereich

Quittie-

rung?

Vorhan-

den?

Übertem-

peratur der 

Elektronik

Soft-

ware

85 °C aus, 

70 °C ein

Ja

Ja

Unter-

spannung

Soft-

ware

10 V aus, 

11 V ein

Ja

Ja

Strombe-

grenzung

Hard-

ware

15 A / 25 A   

Standard

Ja

Blockier-

schutz in 

geregeltem 

Betrieb

Soft-

ware

Ja

Ja

8 Operation hints

8 Betriebshinweise

Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com

Summary of Contents for GR 53 SI

Page 1: ...underutilized and idle equipment along with credit for buybacks and trade ins Custom engineering so your equipment works exactly as you specify Critical and expedited services Leasing Rentals Demos I...

Page 2: ...Instruction Manual Betriebsanleitung Motor with integrated speed controller Motor mit integriertem Drehzahlregler GR 53 SI GR 63 SI Artisan Technology Group Quality Instrumentation Guaranteed 888 88 S...

Page 3: ...5 Teaching of ramps 23 8 6 Function of the pulse output OUT1 25 Seite 1 Inhalt 2 2 ber dieses Dokument 4 3 Allgemeine Beschreibung 5 3 1 Motorbaureihe GR 53 SI 63 SI 5 3 2 Bestimmungsgem e Verwendung...

Page 4: ...29 9 4 Scope of delivery and accessories 29 9 5 Download PDF Data 29 10 Appendix A CE declaration of the manufacturer 30 8 7 Schutzfunktionen und Meldeausgang OUT3 26 8 8 Funktion des Analogeinganges...

Page 5: ...disconnected from the electrical power supply and take precautions to prevent unintentional switching on 2 ber dieses Dokument Die vorliegende Betriebsanleitung stellt Ihnen die SI Antriebe vor und i...

Page 6: ...eine Beschreibung 3 1 Motorbaureihe GR 53 63 SI Bei der Motorbaureihe GR 53 SI 63 SI handelt es sich um DC Motoren b rstenbehaftete Kollektormotoren mit angebauter Drehzahlregelelektronik f r den 4 Qu...

Page 7: ...e sold and used within the European Union 3 2 Bestimmungsgem e Verwendung Die Motoren GR 53 SI 63 SI sind Zulieferteile und d rfen in der beschriebenen Konfiguration in Ma schinen und Anlagen eingeset...

Page 8: ...ect scope with un hindered access 4 Sicherheitshinweise Achtung Vor der Inbetriebnah me sind unbedingt die nachfolgen Sicherheits hinweise zu lesen und zu beachten Eine Nicht beachtung kann zu Ge fahr...

Page 9: ...and water Please see the pin diagram for further information 5 Technische Daten 5 1 Elektrische Daten Nennspannung 12 24V 40V Ungeregelter Drehzahlbereich je nach Motor und Betriebsspannung Regelbare...

Page 10: ...0 1360 1360 Voltage range Max zul ssiger Spannungsbereich VDC 12 40 12 40 12 40 12 40 12 40 Recommended speed control range Empfohlener Drehzahlregelbereich rpm 50 4096 50 4096 50 4096 50 4096 50 4096...

Page 11: ...6 Optionale Anbauten Schneckengetriebe SG Die Schneckengetriebe zeichnen sich durch hohe Laufruhe aus Bei vielen Anwendungen ist die um 90 gegen ber der Motorwelle versetzte Getriebewelle von bauliche...

Page 12: ...onents can be overloaded and destroyed un less suitable measures are ta ken to avoid the occurrence of excessive increased voltages see above filter capacitor 6 2 Elektromagnetische Vertr glichkeit Be...

Page 13: ...r supply and the electronic supply 6 5 Anschlussm glichkeiten Im folgenden werden die Standardanschlussarten mit 12 pol Stecker nochmals explizit dargestellt Die Variante mit 12 pol Stecker bietet den...

Page 14: ...nnection cables of Dunkermotoren See chapter 8 3 for further functions 6 6 1 Anschluss ber 12 pol Stecker bei 12V 24V Ausf hrung Ste cker Pin An schluss Funktion Litzenfarbe der Anschluss leitung mit...

Page 15: ...oren Note Pin connection according to 12V 24V version on request available 6 6 2 Anschluss ber 12 pol Stecker bei 40 V Ausf hrung Stecker Pin An schluss Funktion Litzen farbe der Anschluss leitung mit...

Page 16: ...outputs 6 8 Schematic circuit of the digital inputs 6 7 Prinzipschaltung der Digitalausg nge 6 8 Prinzipschaltung der Digitaleing nge Ausgang Mit max 12 mA belastbar Output Chargeable with max 12 mA 6...

Page 17: ...5 m 3 m 6 m 10 m Standard Angled position not adjustable Gegenstecker mitAnschlussleitung bitte mitbestellen F r die Motoren GR 53 63 SI mit Anschlussstecker 12 polig stehen entsprechende geschirmte u...

Page 18: ...09 Dunkermotoren GmbH D 79848 Bonndorf Germany Option angled position adjustable Option Winkelposition einstellbar 6 Installation terminal assignment 6 Installation und Anschlussbelegung Artisan Techn...

Page 19: ...ong connection of the po wer supply Failure to follow them can result in danger to persons or damage to the machine 7 Anschlussschema Achtung Vor der Inbetriebnahme sind unbe dingt die Sicherheitshinw...

Page 20: ...blue blau brown braun green gr n pink rosa violet violett white wei 42 V DC GND 0V orange Or ange E F G M D red rot red rot black schwarz black schwarz Signals E A Supply Power Logic OUT 1 IN 1 AI AI...

Page 21: ...us OFF IN1 IN2 0 at activated supply voltage 8 Betriebshinweise 8 1 Inbetriebnahme Achtung Vor der Inbetriebnahme sind un bedingt die Sicherheitshinweise zu lesen und zu beachten Eine Nichtbeachtung k...

Page 22: ...mplies with an input level of 0 6 V 1 complies with an input level of 7 24 V 8 2 Funktion der Digitaleing nge IN1 und IN2 Mit Hilfe der beiden digitalen Eing nge IN1 und IN2 lassen sich insgesamt 4 Be...

Page 23: ...ch the second fixed speed repeat this proce dure Die folgenden Betriebszust nde k nnen angesteuert werden IN3 IN4 Funktion 0 0 Drehzahlregelbetrieb ber Analogeingang einstellbar 0 1 Ungeregelter Betri...

Page 24: ...orm see next page 8 5 Teachen von Rampen Falls der Motor die Option bietet Eing nge IN3 IN4 herausgef hrt k nnen die Beschleunigungs und Bremsrampe eingestellt und abgespeichert engl Te achen werden H...

Page 25: ...econd ramp repeat this procedure US Volt z 1024 U 10 Zahl T ms pro 1000 rpm 0 00 0 20000 0 01 1 19531 0 02 2 9766 0 05 5 3906 0 10 10 1953 0 20 20 977 0 50 51 391 1 00 102 195 2 00 205 98 5 00 512 39...

Page 26: ...24 V plus switching with a max permitted current strain of 10 mA 8 6 Funktion des Pulsausgangs OUT1 Der Pulsausgang OUT1 liefert 16 Impulse pro Motor umdrehung wobei die Pulsdauer tP und die Pulspau...

Page 27: ...ion Hard ware 15 A 25 A standard Yes Blocking protection in controlled operation Soft ware Yes Yes 8 7 Schutzfunktionen und Meldeausgang OUT3 Die Schutzfunktionen dienen dem Schutz des Motors vor Zers...

Page 28: ...ed Note A not connected analogue input equals 0 rpm 8 8 Funktion des Analogeinganges AI AI Die Eingangsschaltung des Analogeingangs ist als Dif ferenzverst rker mit einem Eingangswiderstand von 100 kO...

Page 29: ...nsured when disposing of electronic components and gear lubricant 9 Wartung Service 9 1 Motorbetrieb im Q Modus Vor Auslieferung des Motors an den Kunden wird je der Motor im sogenannten Qualit ts Mod...

Page 30: ...4 Scope of delivery and accessories As quoted 9 5 Download PDF Data www dunkermotoren de 9 3 Service Support Bei Fragen und Problemen stehen Ihnen folgende An sprechpartner zur Verf gung Ihre zust nd...

Page 31: ...erg nzende Unterla gen die von der Dunkermotoren oder Drittlieferanten bereitgestellt wurden A CE Herstellererkl rung CE Konformit tserkl rung Hersteller Dunkermotoren GmbH Allmendstra e 11 79848 Bon...

Page 32: ...Manual Betriebsanleitung GR 53 SI GR 63 SI Version 1 2 en_de 2009 Dunkermotoren GmbH D 79848 Bonndorf Germany Notes Notizen Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE ww...

Page 33: ...Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com...

Page 34: ...uipment Have surplus equipment taking up shelf space We ll give it a new home Learn more Visit us at artisantg com for more info on price quotes drivers technical specifications manuals and documentat...

Reviews: