GENERAL
outdoor application and may be mounted on roof or at
Packaged chillers are designed to cool water or other non-
ground level.
corrosive liquids. Water is circulated through the direct
expansion cooler where it is cooled to the desired
Since these units are air cooled, the flow of air to and from
temperature then circulated to cooling coils for air
the condenser coil must not be impeded. There must be no
conditioning, or to other types of heat exchangers for
obstruction above the unit that would tend to deflect
process cooling.
discharge air downward where it could be recirculated back
Care should be taken to see that the equipment is properly
fan outlets.
installed and adjusted. An installer or operator should first
become familiar with the information contained in this
The unit must be installed with sufficient clearance for air
manual.
entrance to the condenser coil and for servicing access.
INSPECTION
wall or other obstruction. See Condenser Clearance
When the equipment is delivered, it is important that the
Drawing page 35. Clearance must be provided at either end
following inspection be completed in the presence of the
of the unit to permit removal of tubes from the chiller.
carrier's representative.
1. Check all crates and cartons received against the Bill of
fume exhausts.
Lading/Shipping Papers to be sure they agree.
2. Check the model number and the electrical
that the unit should be mounted away from noise sensitive
characteristics on the nameplate to determine if they are
spaces and must have adequate support to avoid vibration
correct.
and noise transmission into the building. Units should be
3. Check for freight damage, shortages or other
auxiliary areas where sound levels are not an important
discrepancies and note them on the delivery receipt
factor. Sound and structural consultants should be retained
before signing.
for recommendations on critical installations.
In the event that any damage is found, a damage claim
FOUNDATION
should immediately be filed by the purchaser against the
delivering carrier as all shipments are F.O.B. Factory.
Refer to index for unit dimensions and load points.
RIGGING
functioning of controls and provision must be made for
General - Each unit has been carefully tested and crafted at
dimensions. Roof mounted units must be supported on
the factory where every precaution is taken to assure that
adequate steel structure. If units are located on the ground
the unit reaches you in perfect condition. It is very important
level, a concrete base is recommended.
that the riggers and movers should use the same care and
precaution in moving the equipment into place. Make sure
VIBRATION ISOLATION
that chains, cables, or other moving equipment are placed
so as to avoid damage to the unit or piping. The refrigerant
Under certain critical conditions, it may be necessary to
piping must not be used as a ladder or as a hand hold. Do
install vibration isolators under the base of the Packaged
not attach a chain hoist sling to the piping or equipment.
Chiller.
Move the unit in an upright position and let it down gently
from trucks or rollers.
Rubber-in-shear or spring vibration isolators are offered as
Rigging and Moving - Any unit mounted on skids may be
connections must be installed in the water piping system
moved with a forklift, but care must be taken not to damage
and in the refrigerant lines of split systems. Note: These
the unit with forks. The skids should not be removed until
flexible connectors must be suitable for the fluid and
the unit is at its final location.
pressures involved.
The ACDX/AUDX 040-060 units are to be rigged thru the
All piping which is external to the packaged chiller must be
small holes at the bottom of each leg. On units with optional
supported by spring mounted hangers and any piping which
louvers, it will be necessary to remove labeled louver panels
goes through the wall, ceiling or floor should be properly
to gain access to the rigging holes. Models 080 thru 255 are
sheathed to prevent transmission of piping vibration to the
to be rigged thru the holes in the base side rails. In all
structure.
cases, spreader bars must be used between rigging lines to
prevent coil or fan deck damage. The unit must be lifted
When spring isolators are used, electrical service to the unit
using All Rigging Points. Refer to Rigging Instructions on
must also be flexibly connected, by means of a 36" section
page 36.
of flexible conduit.
All models can be pushed or pulled (with chains) from the
PIPING CONNECTIONS
control box end only. Truck forks must be kept level and not
tilted back. Do not raise the end of the unit more than 2" off
the floor.
LOCATION & MOUNTING
Model ACDX Air Cooled Packaged Water Chillers and
AUDX Air Cooled Condensing Units are designed for
3
to the inlet of the unit. Ductwork must not be applied to the
The unit should be located no closer than four feet from any
Units must not be located in the vicinity of steam, hot air or
Another consideration which must be taken into account is
mounted over corridors, utility areas, rest rooms or other
Foundations must be level for proper operation and
supporting the individual load points as shown in the unit
optional items. When spring isolators are used, flexible
Water Connections, Chilled Water Piping - After the unit
has been leveled, the external water piping may be made
up. Be sure water piping is connected to the correct fittings.
The water out connection is closest to the expansion valve
(R-in) end. A chilled water flow switch must be installed in
the external chilled water outlet piping.
Summary of Contents for ACDX
Page 25: ...TYPICAL POWER WIRING ACDX120A...
Page 26: ...TYPICAL CONTROL WIRING ACDX120A...
Page 27: ...TYPICAL OPTIONS WIRING ACDX120A...
Page 28: ...TYPICAL CONTROL WIRING ACDX120B W MICRO...
Page 29: ...TYPICAL CONTROL WIRING ACDX120B W MICRO...
Page 30: ...TYPICAL OPTIONS WIRING ACDX120B W MICRO...
Page 33: ......
Page 34: ...ACDX AUDX CONDENSER CLEARANCE...
Page 35: ......
Page 36: ...ACDX LOAD POINTS...
Page 37: ...ACDX RUBBER IN SHEAR ISOLATOR...
Page 38: ...ACDX SPRING ISOLATOR...
Page 39: ...AUDX LOAD POINTS...
Page 40: ...AUDX RUBBER IN SHEAR ISOLATOR...
Page 41: ...AUDX SPRING ISOLATOR...