4.22
High Motor Temperature Safety
4.24
High Discharge Pressure Unload
If the high motor temperature switch of a
This function unloads the compressor if
compressor opens, the motor temperature
discharge pressure is approaching the high
digital input turns ON. If the compressor is
pressure limit. If discharge pressure of an
operating, the compressor will be locked off.
operating compressor reaches the high
The high motor temperature alarm will be
pressure setpoint minus 10 psi, the
recorded by the computer and RESET must
compressor will be prevented from loading
be pressed after the problem is resolved.
(HOLD state). If the discharge pressure
4.23
Low Chiller Flow Alarm
A low flow alarm will be generated if a
compressor control point is ON and the flow
switch digital input is OFF. All compressors
This function unloads the compressor if suction
will be locked off and the alarm light turned
pressure is approaching the low pressure limit.
on. After resolving the problem, press
If suction pressure reaches the low pressure
RESET.
setpoint plus 4 psi, the compressor will be
reaches the high pressure setpoint minus 5
psi, the compressor will begin unloading.
4.25
Low Suction Pressure Unload
prevented from loading (HOLD state). If
suction pressure falls to the suction pressure
setpoint plus 2 psi, the compressor will begin
unloading.
23
Summary of Contents for ACDX
Page 25: ...TYPICAL POWER WIRING ACDX120A...
Page 26: ...TYPICAL CONTROL WIRING ACDX120A...
Page 27: ...TYPICAL OPTIONS WIRING ACDX120A...
Page 28: ...TYPICAL CONTROL WIRING ACDX120B W MICRO...
Page 29: ...TYPICAL CONTROL WIRING ACDX120B W MICRO...
Page 30: ...TYPICAL OPTIONS WIRING ACDX120B W MICRO...
Page 33: ......
Page 34: ...ACDX AUDX CONDENSER CLEARANCE...
Page 35: ......
Page 36: ...ACDX LOAD POINTS...
Page 37: ...ACDX RUBBER IN SHEAR ISOLATOR...
Page 38: ...ACDX SPRING ISOLATOR...
Page 39: ...AUDX LOAD POINTS...
Page 40: ...AUDX RUBBER IN SHEAR ISOLATOR...
Page 41: ...AUDX SPRING ISOLATOR...