background image

It must be located in a horizontal section on the pipe where

Method B.  Install units the same as Method A, but add a

there are at least five (5) pipe diameters on both sides of the

third thermostat in the return water, as shown in Figure 1E.

flow switch before any other connections.  The flow switch

This thermostat will be set to cycle off one of the units when

paddle must be adjusted to the size pipe in which the paddle

the load drops below 40%.  When this condition is reached,

is installed.  Consult the wiring diagram accompanying the

leaving mixed water temperature will rise, causing the return

unit for the electrical connections to interlock the flow switch

water temperature to rise and the unit operating will load up.

with the control panel.

The "off" unit is sequenced to start again before full system

Water flow through the cooler must remain constant for
proper chiller operation.  Water pressure gauges are

This system will not provide as stable an operation as

recommended to check the water pressure and flow rate in

Method A, but in normal air conditioning applications, this is

the system, before and after the cooler, and to determine if

not detrimental.  The advantage of Method B is a better part

variations occur in the cooler and system.

load efficiency.

If sub-freezing ambient temperatures are possible, all

Series Chilled Water Flow Units - Units should be equally

exposed field water piping should have heater tape and

sized.  The upstream unit will carry a larger load because it

insulation or a glycol mixture to prevent freezing.  Main

cools higher temperature water.  The controllers are to

power is required to keep the sump heaters on.  A separate

sense leaving water temperatures (see Figure 1D).  The

115 volt circuit is required for the chiller heaters.

number 1 unit controller should be set to start the unit at

When installing pressure taps to measure the amount of

minimum loading of the number 1 unit times unit number 1

pressure drop across the water side of the cooler, the taps

design temperature differential [example:  system design

should be located in the water piping a minimum of twenty-

supply water temperature is 45

E

F, design temperature

four (24) inches downstream from any connections (flange,

differential is 12

E

F; Unit #1 minimum loading is 15% and the

elbow, etc.).

design temperature difference is 6.5

E

F: (.5 x 12) + (.15 x

There are many piping and control systems which may be

set to cycle the unit off at system supply water temperature

used to assure constant water flow through the cooler.  A

plus number 2 unit design temperature differential times .9

typical system is shown in Figure 1A.  It uses a three way

[example: 45

E

F + (.9 x 5.5) = 50

E

F]. These settings will

motorized valve which operates in response to the

ensure enough load on the number 1 unit to prevent short

discharge air temperature of the cooling coil.

cycling. 

Another system which is sometimes used consists of a two

The above series flow controller set points are for the

way modulating control valve, which also responds to the

electromechanical units. Contact the factory for

discharge air temperature of the cooling coil, used in

microcomputer controlled units.

conjunction with a spring loaded bypass regulating valve as
shown in Figure 1B.  The bypass valve must be set to

Water Quality ACDX  - Coolers used in these packages are

assure the full flow of circulating chilled water when the

made of steel, copper and brass and are suitable for

modulating valve is completely closed.

operation with well-maintained water systems.  However, if

Other systems are noted in the ASHRAE Handbook and

or entrained solids, the water can cause reduced

may serve equally well.  Whatever system is selected, water

performance and even failure of heat exchangers.

flow must be constantly maintained through the chiller.

Therefore, it may be necessary to obtain the services of a

If the system is arranged for the dual purpose of cooling in

water treatment.  This is particularly important with glycol

the summer and heating in the winter, THE COOLER MUST

systems.

BE VALVED OFF DURING THE HEATING SEASON SO
THAT HOT WATER WILL NOT PASS THROUGH THE

For information concerning the installation, operation and

COOLER.  THIS MAY BE EITHER A MANUAL OR

servicing of Dunham-Bush coolers, consult the latest

AUTOMATIC CHANGE-OVER OPERATION.  There are

revision of Form 8110.

also times, such as early spring and late fall, when both
heating and cooling are required.  This should also be

AUDX AIR COOLED CONDENSING UNIT PIPING

considered when designing heating and cooling systems.

The suction and liquid line sizing should be in accordance

For various piping arrangements, consult the ASHRAE

with ASHRAE recommendations.  Following is a list of

Handbook.

requirements for split systems:

Water Connections - Multiple Packaged Chillers -

1. The evaporator must be within 50 ft. of the condensing

Multiple unit packaged chillers have been successfully

unit.

applied to parallel and series piping systems for years.

2. There should be no more than an 18 inch rise in the

Special attention, however, must be given to the particulars

suction line.

involved for each application or serious operational

3. The system piping must be submitted to Dunham-Bush,

problems can result.

Inc. for review.

The following are guidelines which should be followed for

authorized service agency.

multiple unit application.  NOTE:  A constant chilled water
flow rate is assumed to be maintained through all coolers.

The unit is supplied with a suction filter to protect the

Parallel Chilled Water Flow Units - Method A.  Both units
operate simultaneously, modulating with load variations.
Each packaged chiller operating controller senses leaving
water temperature using standard controls (see Figure 1C).
The set point of each controller will be set to maintain the
desired unloading.  

load temperature is reached.

system design leaving water temperature plus 50% of the

6.5) +45 = 52

E

F].  The number 1 unit controller should be

the water used in cooler is corrosive, high in mineral content

water treatment consultant and to provide and maintain

4. The system should be started by a Dunham-Bush, Inc.

compressor from dirt, etc., which may have gotten into the
system low side components.  THE FILTER SHOULD BE
REMOVED FROM THE SYSTEM AFTER A WEEK'S
RUNNING.
  This will allow plenty of time for system clean
up.  Leaving the filter in the system will cause an increased
pressure drop in the suction line and decrease the unit
capacity and efficiency.

     

4

Summary of Contents for ACDX

Page 1: ...ctions 6 ACDX Operation Start up 6 7 Maintenance 7 Slide Valve Unloading Operation 8 Low Ambient Operation 9 Fan Position Numbers 10 Fan Cycling Sequence 11 ACDX Sequence of Operation 12 Electrical Co...

Page 2: ...rs attention to the instructions contained herein it will give To use this manual effectively you must first identify your unit model from the unit nameplate It is assumed the user of this manual and...

Page 3: ...eration Weight 3592 4732 5044 7712 9684 10726 MODEL SIZE 150 170 185 210 235 255 Compressor Model Qty SSCA060 3 SSCA075 3 SSCA060 4 SSCA075 4 SSCA060 1 SSCA060 2 SSCA075 2 SSCA075 2 Displ CFH Compr 72...

Page 4: ...cables or other moving equipment are placed so as to avoid damage to the unit or piping The refrigerant Under certain critical conditions it may be necessary to piping must not be used as a ladder or...

Page 5: ...microcomputer controlled units conjunction with a spring loaded bypass regulating valve as shown in Figure 1B The bypass valve must be set to Water Quality ACDX Coolers used in these packages are ass...

Page 6: ...5 TYPICAL CHILLED WATER PIPING TYPICAL MULTIPLE PACKAGED CHILLED WATER CONNECTIONS PARALLEL FLOW PARALLEL FLOW SERIES FLOW...

Page 7: ...ump temperature must be at a The unit is ready for start up when the following procedures representative This will ensure that the oil is warm have been completed enough to vaporize any dissolved refr...

Page 8: ...Compressor Models SSCB use DB Karlube 21 Oil Contact factory for price The above listed oils are synthetic lubricants of the Polyol Ester POE type Due to the complex nature of the POE great precaution...

Page 9: ...en or close UL 1 and UL 2 in response to the supply water temperature The slide valve will move to the left loading by force of discharge pressure whenever UL 1 opens to permit flow to the oil return...

Page 10: ...ell as that portion of the surface rejecting heat by natural convection with related fans off To further assist low ambient starts all fans are held off until the head pressure reaches 190 psig This a...

Page 11: ...C1 1 3 5 7 9 11 C2 2 4 6 8 10 12 150 1 2 150 3 C1 1 3 5 7 9 11 13 15 C3 C2 2 4 6 8 10 12 14 16 Front Rear 170 1 2 170 3 185 1 2 185 3 C1 1 3 5 7 9 11 13 15 17 C3 C2 2 4 6 8 10 12 14 16 18 Front Rear...

Page 12: ...1 RH 2 4 6 8 10 12 1 LH 1 3 5 7 9 11 2 LH RH 13 14 15 16 17 18 Rear Module 185 1 RH 2 4 6 8 10 12 1 LH 1 3 5 7 9 11 2 LH RH 13 14 15 16 17 18 Rear Module 210 1 LH 1 3 5 7 9 Rear Module 1 RH 2 4 6 8 1...

Page 13: ...M1 1 opens to de energize oil light is not on disconnect the main power and reverse sump heater 1HTR and switch 1M1 2 closes to any two phase legs at the Main Incoming Power activate the fan control c...

Page 14: ...ed Compressor No 2 will not be able to restart for five minutes due to integral time delays SAFETY CONTROLS The unit is protected by the following safety controls 8 Water Flow Switch FLS 1 High Pressu...

Page 15: ...occurs temperature during the compressor off when ambient temperature is below 40EF cycle preventing refrigerant migration in 3TAS is measuring ambient temperature to the crankcase and consequent and...

Page 16: ...ges 27 1TAS Motor Overload Protection Compressor overload protection is 1 Unit Control Contact Unit on off control should be provided by a solid state device 1TAS done through the terminals shown on t...

Page 17: ...ps Electrically Programmable Read Only an NC25 microcomputer system The computer Memory store general operating procedures system is composed of a main microcomputer algorithms and is the same for all...

Page 18: ...nce midnight and the accumulated run time during yesterdays Y twenty four hour period CYC gives the number of times that the control point cycled off since midnight If a feedback digital input is asso...

Page 19: ...then new calibration would be 58 60 3 1 3 3 3 So the zero calibration should be changed to 3 1 You must be authorized See Section 3 4 2 Select DATE TIME SET on the main menu Press ENTER to display cur...

Page 20: ...r start delay 7 Power loss reset 8 Anti recycle timing 9 Low pressure safety 19 11 Freeze safety 12 High Oil Temp Safety 13 Alarm Output 14 Fan control 15 Chilled water reset and customer control inte...

Page 21: ...rough 4 for each compressor number manual control DO NOT start a compressor 7 Add the value obtained in step 5 to the amps calculation A setpoint value from step 6 NOTE All compressors will revert bac...

Page 22: ...rator pressure of a given Sample Ramp Times Minutes For a Two pressure B setpoint a time delay is initiated If Compressor Unit with a 2 Second Compressor the pressure stays below the setpoint during t...

Page 23: ...ow normal compressor control if the unit schedule is calling for unit operation that a compressor auxiliary contact digital input stays ON for 15 seconds when the computer is commanding the compressor...

Page 24: ...e pressed after the problem is resolved HOLD state If the discharge pressure 4 23 Low Chiller Flow Alarm A low flow alarm will be generated if a compressor control point is ON and the flow switch digi...

Page 25: ...TYPICAL POWER WIRING ACDX120A...

Page 26: ...TYPICAL CONTROL WIRING ACDX120A...

Page 27: ...TYPICAL OPTIONS WIRING ACDX120A...

Page 28: ...TYPICAL CONTROL WIRING ACDX120B W MICRO...

Page 29: ...TYPICAL CONTROL WIRING ACDX120B W MICRO...

Page 30: ...TYPICAL OPTIONS WIRING ACDX120B W MICRO...

Page 31: ...5 472 12 1 5 5 9 400 3 4 1120 9 3 460 257 350 75 2 98 539 180 12 1 5 3 0 400 3 4 1120 9 3 150 230 570 700 60 3 152 1228 409 16 1 5 5 9 600 5 0 1120 9 3 208 632 800 60 3 171 1228 409 16 1 5 5 9 600 5 0...

Page 32: ...Cooler Model Curve No Min GPM Max GPM 040 CHSO10601B 1 78 315 050 CHS011601B 1 86 315 060 CHS013601B 2 101 420 080 EXD14102J09 3 140 440 095 EXD16112J09 4 175 519 120 EXD16122J07 5 236 697 150 EXT181...

Page 33: ......

Page 34: ...ACDX AUDX CONDENSER CLEARANCE...

Page 35: ......

Page 36: ...ACDX LOAD POINTS...

Page 37: ...ACDX RUBBER IN SHEAR ISOLATOR...

Page 38: ...ACDX SPRING ISOLATOR...

Page 39: ...AUDX LOAD POINTS...

Page 40: ...AUDX RUBBER IN SHEAR ISOLATOR...

Page 41: ...AUDX SPRING ISOLATOR...

Page 42: ...4 Clean the condenser 5 Compressor discharge check valve not operating 5 Replace if necessary properly 6 Fans not running 6 Check pressure control setting condenser pressure exceeds saturated pressure...

Page 43: ...Start Up a Open compressor discharge service valve if supplied b Open liquid valve s c Open suction and discharge valves to pressure gauges if supplied d Check rotation of all fan motors e Start auxi...

Page 44: ...101 Burgess Road Harrisonburg VA 22801 PH 540 434 0711 FAX 540 434 4595 Printed in U S A I O 6193A Issued 9 98...

Reviews: