KEY TO WIRING DIAGRAM INDEXING SYSTEM
The wiring diagrams and sequence instructions on the following pages have been devised to simplify the
understanding and tracing of circuit theory. The following key shows how the indexing system can be used.
9
Line number on wiring diagram
[9]
Line number in text
(1CR)
Component identification symbol in text (Control Relay #1)
(50)
Normally open contact -- line number location
(1)
Normally closed contact -- line number location
SEQUENCE OF OPERATION (TYPICAL)
MODELS ACDX40-120 A GENERATION
(Ref. Typical Wiring Diagrams on pages 26, 27 & 28)
The following sequence of operation is typical of all
to the desired leaving water temperature (e.g. 44
E
F).
electromechanical ACDX Models. Refer to the wiring
Set point adjustment is accomplished directly on the
diagram furnished with the unit for specific
control. Initial control band setting is 4.0.
information.
( )
Control Identification Symbol
S3) in the "On" position, thus energizing the balance
[ ]
Circuit Line Number
of the control circuit. All safety controls must be
Important Note!
for five minutes before the first compressor will start.
With all the control circuit switches (S1-S3) in the "off"
position, Terminals #1 and #2 on the Terminal Board
Stage 1 Starting
(3TB) must have 115 volts supplied for a minimum of
Upon demand for cooling, the first step of the staging
24 hours to energize the compressor crankcase
thermostat (4TAS) will close energizing relay (8CR).
heaters (1HTR, 2HTR).
If all the safety controls and switches are closed, (see
Preliminary Sequence
contactors for Compressor No. 1 will energize and the
Close the main power disconnect switch. Check to
compressor will start. The liquid line solenoid (1SOL)
see that the indicating light on the under voltage relay
will also be energized and refrigerant flow starts.
(UVR) is lit. This light must be on to indicate
proper phase rotation for the compressors. If the
Auxiliary switch (1M1-1) opens to de-energize oil
light is not on, disconnect the main power and reverse
sump heater (1HTR) and switch (1M1-2) closes to
any two phase legs at the Main Incoming Power
activate the fan control circuit.
Terminal Block. (WARNING! DO NOT REVERSE
THE LEADS ON THE PHASE LOSS MONITOR FOR
The fan motors are controlled by fan cycling controls
THIS WILL ALLOW THE COMPRESSORS TO RUN
(10PS-1,2,3 & 4) and will cut in at the factory set
BACKWARDS, CAUSING SEVERE DAMAGE, AND
condenser pressures shown on the wiring diagram.
WILL VOID THE COMPRESSOR WARRANTY!)
The crankcase heater relay contacts (1M1-1) and
begins timing. If suction pressure does not rise above
(2M1-1) are closed and are supplying power to the
setpoint within 120 seconds, the compressor will be
compressor crankcase heaters. Power must also be
shut down.
supplied to the chiller heater (CHR HTR) by the
separate customer supplied 115 VAC supply.
Timer (7TR-1) contacts stay in the NC position to
Control power is turned on by the Control Power
the compressor in the full unload position for 30
Switch (S1). UVR contacts must close to activate
seconds. After (7TR-1) times out (30 seconds), the
1CR and temperature freezestat (2TAS) must also be
contacts for the fast unloader solenoid (2SOL) open
satisfied to allow compressor operation.
and the NO contacts close, which energizes the relay
Start up the chilled water pump. The water flow is
confirmed when the water flow switch completes the
Stage 1 Modulation
electrical circuit across Terminals #8 and #9 and
Upon energizing relay coil (2CR), the NO contacts of
when chilled water pump auxiliary (CWP) closes
relay (2CR) are closed, allowing the thermostat
between #9 and #10.
(4TAS) to energize the load solenoid (3SOL) and the
Check to make sure time clock contacts close during
occupied modes and then set the thermostat (4TAS)
Place the two compressor control circuit switches (S2-
satisfied and the system may be in a "Time-in" mode
"Safety Controls" section for more detail) the
If suction pressure is low, pressure switch (9PS-1)
power the fast unloader solenoid (2SOL) which holds
(2CR).
unload solenoid (7SOL) upon demand.
12
Summary of Contents for ACDX
Page 25: ...TYPICAL POWER WIRING ACDX120A...
Page 26: ...TYPICAL CONTROL WIRING ACDX120A...
Page 27: ...TYPICAL OPTIONS WIRING ACDX120A...
Page 28: ...TYPICAL CONTROL WIRING ACDX120B W MICRO...
Page 29: ...TYPICAL CONTROL WIRING ACDX120B W MICRO...
Page 30: ...TYPICAL OPTIONS WIRING ACDX120B W MICRO...
Page 33: ......
Page 34: ...ACDX AUDX CONDENSER CLEARANCE...
Page 35: ......
Page 36: ...ACDX LOAD POINTS...
Page 37: ...ACDX RUBBER IN SHEAR ISOLATOR...
Page 38: ...ACDX SPRING ISOLATOR...
Page 39: ...AUDX LOAD POINTS...
Page 40: ...AUDX RUBBER IN SHEAR ISOLATOR...
Page 41: ...AUDX SPRING ISOLATOR...